Raypak VERSA IC Installation & Operating Instructions Manual page 14

Integrated boiler control
Table of Contents

Advertisement

Enable followers from appropriate BOILER menu at the master:
Item
BOILER 1, 2, 3, 4
ON <> OFF
The following settings are available in the SETUP/ADJUST Menu:
Item
Reset - Setpoint
Target
Mode
XFYRE 50 TO 192°F
XPAKFT 50 TO 192°F
SETPOINT
MVB/XTHERM 50 TO
Target Max.
XPAK FT 190°F
MVB/XTHERM 220°F
Target Min.
Sys. Purge
0:20 to 20:00 min
Units
When RESET from target screen is selected the following items will be available for adjustment:
Out Start
Out Design
Boil Start
Boil Design
WWSD
When manual differential is selected via PIM™ DIP switch #1, the following item will appear:
Target Diff
Range
Default
OFF
Range
Default
EMS
SETP
Modbus
1 - 2 - 3
180°F
220°F
XFYRE 190°F
192°F
192°F
220°F
50 to 180°F
0:20 min
F or C
35 to 85°F
-60 to 45°F
35 to 150°F
70 to 200°F
180°F
40 to 100°F
2 to 42°F
User Settings
User Settings
1
50°F
F
70°F
10°F
70°F
70°F
10°F
14
When is it
Description
Displayed
Cascade Followers
FT_Bus 1, 2, 3,4
present
are connected
When is it Displayed
RSET = Outdoor Reset
SETP = Setpoint
PIM™ Identity is H
EMS = Energy
EMS = Temp/Rate
Management System
Modbus = Temp/Rate
(Analog Target
MODB = Modbus
PIM™ Identity is H
Piping and application
TARGET = Rset or Setp
Piping and application
PIM™ Identity is H
Modbus Rate
Maximum Target Boiler
EMS Rate
PIM™ Identity is H
Modbus Rate
Minimum Target Boiler
EMS Rate
PIM™ Identity is H
Modbus
Sets the length of the
Temp/Rate
System Pump Purge
PIM™ DIP = Purge On
Show Units Using Icons
Always
PIM™ Identity is H
Outdoor Reset Starting
Target = Rset
PIM™ Identity is H
Outdoor Reset Design
Target = Rset
Starting Boiler Target
PIM™ Identity is H
Temperature when
Target = Rset
Outdoor Temperature is
at Outdoor Start
Design Boiler Target
Temperature when the
PIM™ Identity is H
Outdoor Temperature is
Target = Rset
at Outdoor Design
(Hottest Water on
The System Warm
Target = Rset
Weather Shut Down
PIM™ Identity is H
PIM™ Identity is H
Differential for Target
PIM™ DIP = Manual Diff
Boiler Temperature
Description
Temperature)
configuration
configuration
Temperature
Temperature
in Display
Temperature
Temperature
Coldest Day)
Temperature