FAULT DESCRIPTION
SENT TO Ul
RESET TIME
(minutes)
--
ON, no flash
- -
1, pause
1 (2 sec ON), longer pause
(1
second OFF)
Communications
Loss
NA
Invalid Model
NA
High Pressure
Switch Open
15
Low Pressure
Trip
15
Control
Fault
NA
Brownout
Revert to 5 min cycle delay
Lost Inverter Communications
Revert to 5 min cycle delay
230VAC Dropout-Reset
Event
Revert to 5 min cycle delay
Outdoor Air Temp Sensor Fault
NA
Suction Temp Sensor Fault
15
Coil Temp Sensor Fault
NA
OAT-OCT
Thermistor
Out of range
NA
Suction Pressure
Sensor
Fault
15
OAT-OST
Thermistor
Out of range
5
Compressor
Scroll Temp Out of Range
15
Compressor
Sump Heating Active
2 HOURS
Inverter / Compressor
Internal
Fault
15
Compressor
Motor Temp Out of Range
15
Suction Over Temperature
15
Inverter Temp Out of Range Event
15
Inverter
Over Current
15
Compressor
No-Pump
Event
15
Suction Over Temp Lockout
4 Hours
Low Pressure
Lockout for 4 hours
4 HOURS
High Pressure
Lockout for 4 hours
4 HOURS
Compressor
Temp Lockout
4 HOURS
Compressor
Temp Sensor Fault
15
Inverter Temp Lockout
4 HOURS
Inverter VDC-Out
Over Voltage
15
Inverter VDC- Out Under Voltage
15
230VAC Under Voltage
15
230VAC Over Voltage
15
High Current
Lockout
2 HOURS
VDC Under Voltage Lockout
2 HOURS
VDC Over Voltage Lockout
2 HOURS
High Torque Event
10
High Torque Lockout
2 HOURS
--
NA
Table 7 - Troubleshooting
FLASH CODE
(AMBER LED)
Standby
Variable Capacity or Emergency
Mode
Variable Speed Range Cutback
16
25
31
32
45
46
48
49
53
54
55
56
57
58
59
68
69
71
72
75
77
79
82
83
84
85
86
88
91
92
93
94
95
96
97
98
99
OFF
17