Temperature-Pressure Relief Valve-Optional Location - Kenmore 153.326164 Use & Care Manual

30 / 38 gallon short
Table of Contents

Advertisement

made withanyliveelectrical part. T he discharge opening m ust
notbeblocked o r reduced i nsizeunder a nycircumstances.
Excessive length, over30feet(9.14 m),or useofmore than
fourelbows cancause restriction andreduce thedischarge
capacity ofthevalve.
Water Damage Hazard
• Temperature-pressure
relief valve discharge
pipe must terminate at adequate drain.
HOT
SHUT-OFF
VALVE
COLD
No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided.
To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances
demand. Ifthe discharge pipe is not connected to a drain or other
suitable means, the water flow may cause property damage.
The Discharge Pipe:
Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
Shall not be plugged or blocked.
Shall be of material listed for hot water distribution.
Shall be installed so as to allow complete drainage of both the
temperature-pressure
relief valve, and the discharge pipe.
Shall terminate at an adequate drain.
• Shall not have any valve between the relief valve and tank.
t!t m7:1
=1
Water
temperature
over
125°F
(52°C) can cause severe
burns
instantly resulting in severe injury
or death.
Children,
the elderly,
and
the
,_
physically
or mentally
disabled
.
are at highest riskfor scald injury.
_,,_,
Feel
water
before
bathing
or
_
1_
showering.
Temperature
limiting valves
are
available.
Read instruction
manual for safe
temperature setting
The temperature-pressure
relief valve must be manually operated
at least once a year. Caution should be taken to ensure that
(1) no one is in front of or around the outlet of the temperature-
pressure relief valve discharge line, and (2) the water manually
discharged wilt not cause any bodily injury or property damage
because the water may be extremely hot.
If after manually operating the valve, it fails to completely reset
and continues to release water, immediately close the cold water
inlet to the water heater, follow the draining instructions, and
replace the temperature-pressure
relief valve with a new one.
CONDUIT
j
FLOOR
DRAIN(_
TEMPERATURE-
PRESSURE
RELIEF
VALVE LOCATION
k_"
TEMPERATURE-
PRESSURE
RELIEF
VALVE
_
DISCHARGE
PIPE
(DO NOT CAP
OR PLUG)
o
FIGURE 10.
Temperature-Pressure
Relief Valve -
Optional
Location
An optional temperature-pressure
relief valve location is provided
on the jacket top.
If the top location is preferred, the temperature-pressure
relief
valve in the side location and the counter-sunk
plug in the top
location can be interchanged.
Be sure to use new pipe joint compound or put two to three turns
of teflon tape around the threaded
ends of the temperature-
pressure relief valve and counter-sunk
plug when reinstalling
these parts.
¢Z3
TEMPERATURE-
COLD,
_
PRESSURE
HOT
_
_-]J_RELIEF
_
SHUT-OFF
_VALVE
VALVE
_
I_1
DISCHARGE
I
11
I
PIPE
I
II
I,'(D° NOTCAP
BACK SIDE _._
I
_
AIR
GAP
FLOOR
DRAIN _
--
12
FIGURE 10A.