Summary of Contents for Ever SINLINE PRO 10000

  • Page 2: Table Of Contents

    Instruction manual for SINLINE PRO 10000 series power supply units TABLE OF CONTENTS TABLE OF CONTENTS............................2 INTRODUCTION ..............................3 GENERAL INFORMATION ..........................3 INTENDED APPLICATION..........................3 GENERAL DESCRIPTION ..........................4 STRUCTURE ................................. 7 USER INTERFACE............................8 SCREENS ................................ 10 Main menu ................................
  • Page 3: Introduction

    The UPS EVER SINLINE PRO 10000 has been designed in such a way as to best meet all your expectations regarding protection against the consequences of power outages.
  • Page 4: General Description

    Instruction manual for SINLINE PRO 10000 series power supply units GENERAL DESCRIPTION • Sinusoidal output voltage, generated in battery operation mode; • DPC (Digital Power Control) - Digital control of the power supply units operating parameters, such as: - output voltage shape,...
  • Page 5 Instruction manual for SINLINE PRO 10000 series power supply units Figure 1: Simplified block diagram of the power supply unit The SINLINE PRO 10000 power supply unit is a modern electronic device that serves as an autonomous source of sinusoidal 230 V voltage. The device belongs to the LINE–INTERACTIVE (VI) class of UPSs, which includes power supply units that...
  • Page 6 The DPC system supports various methods of communication between the unit and a PC over a communication link or a special link for the connection of an EVER management card EVER (HTTP, telnet, SNMP). The unit performs precise measurements of its basic parameters, including battery...
  • Page 7: Structure

    Instruction manual for SINLINE PRO 10000 series power supply units STRUCTURE 1) BYPASS switch cover 2) Fans 3) Adapter card slot plug 4) USB communication link 5) RS232 communication link 6) EPO link 7) Fusible cut-out for internal batteries 8) Connection links cover...
  • Page 8: User Interface

    Instruction manual for SINLINE PRO 10000 series power supply units USER INTERFACE The user interface consists of a four-button keypad located on the upper cover of the power supply unit, an LCD, and three LEDs. They allow the user to monitor the unit's operating parameters, and also modify some of them.
  • Page 9 Instruction manual for SINLINE PRO 10000 series power supply units www.ever.eu 2010/08/24...
  • Page 10: Screens

    Instruction manual for SINLINE PRO 10000 series power supply units SCREENS SCREENSAVER Description: An information screen that is activated 5 minutes after the last press of a button. This is accompanied by the switching off of the LCD panel's backlight.
  • Page 11: Measurements Submenu

    Instruction manual for SINLINE PRO 10000 series power supply units The main menu comprises tree screens. Switching between screens is effected by means of the ▼▲ keys. A selection is confirmed by pressing the key, whereafter a submenu may be selected in the chosen menu also by means of the ▼▲ keys.
  • Page 12 Instruction manual for SINLINE PRO 10000 series power supply units Screen view: BATTERY 3/4 Description: Battery-related parameters Type: read Parameters – battery section voltage – absolute battery current value – charge level of batteries (calculated for the current load) – anticipated autonomous time StanAku.
  • Page 13: Control Submenu

    Instruction manual for SINLINE PRO 10000 series power supply units CONTROL submenu The CONTROL submenu is divided into three groups. The menu can be navigated in the same way as described above. The user may alter the configuration of the power...
  • Page 14 Instruction manual for SINLINE PRO 10000 series power supply units CONTROL 1/3 Description: Settings of power supply unit control flags. Type: read/save Parameters AwaryjneWylaczenie – forced passage of the power supply unit to the EPO mode from the user interface level –...
  • Page 15: Configuration Submenu

    Instruction manual for SINLINE PRO 10000 series power supply units CONFIGURATION submenu The CONFIGURATION submenu is divided into four groups. The menu can be navigated in the same way as described above. The user may change the power supply unit parameter values if the keypad is not locked.
  • Page 16 Instruction manual for SINLINE PRO 10000 series power supply units CONFIGURATION 3/4 Description: Power supply unit parameters Type: read/save Parameters Poj. z STB. – minimal charge level that the batteries must attain in order for the power supply unit to start up following a discharge ProgKas.Prz.
  • Page 17: Alarms Submenu

    Instruction manual for SINLINE PRO 10000 series power supply units ALARMS submenu The ALARMS submenu comprises two screens. The menu can be navigated in the same way as described above. Screens are selected using the ▲▼ keys, and confirmation given by pressing .
  • Page 18: Statistics Submenu

    Instruction manual for SINLINE PRO 10000 series power supply units STATISTICS submenu The STATISTICS submenu comprises four screens. The menu can be navigated in the same way as described above. Screens are selected using the ▲▼ keys, and confirmation given by pressing .
  • Page 19 Instruction manual for SINLINE PRO 10000 series power supply units STATISTICS 3/4 Description: Statistical data. Type: read Parameters Rozładowan – the number of total discharges of the power supply unit's batteries AVR Podw. – the number of activations of the AVR system resulting in an increase in voltage value AVR ObniŜ.
  • Page 20: Panel Settings Submenu

    Instruction manual for SINLINE PRO 10000 series power supply units PANEL SETTINGS submenu The PANEL SETTINGS submenu contains a single screen. The menu can be navigated in the same way as described above. The user can change the values of power supply unit parameters.
  • Page 21: Industrial Work Safety Instructions

    (storage cells), and therefore a dangerous voltage may appear on the output even if it is not connected to the mains. NOTE! SINLINE PRO 10000 power supply units are not intended for usage with medical life and/or health support systems.
  • Page 22: Installation

    Instruction manual for SINLINE PRO 10000 series power supply units INSTALLATION NOTE! Before installing the appliance, you must acquaint yourself with the principles of industrial work safety set forward in the previous chapter. UNPACKING Carry out a visual inspection of the power supply unit immediately upon delivery.
  • Page 23: Installation Of The Power Supply Unit

    Figure 2: Mounting holders BATTERY MODULE Additional battery modules can be connected to the SINLINE PRO 10000 series power supply units. The modules are attached to the connection terminals on the rear panel of the unit. Adding additional battery packs extends the time of battery mode operation.
  • Page 24: Connecting Modules

    Instruction manual for SINLINE PRO 10000 series power supply units Figure 3: Connecting battery modules Connecting modules Note! When the safeguards are active, the voltage on the connection terminals is dangerous to health and/or life. All safeguards must be switched off before carrying out any installation work! 1.
  • Page 25: Disconnecting Modules

    Instruction manual for SINLINE PRO 10000 series power supply units 10. Replace the fuse-elements in their respective mounts. 11. Close the fusible cut-out mounts of all connected battery modules in turn. 12. Close the F1 mount in the power supply unit.
  • Page 26: Connecting The Power Supply Unit

    Instruction manual for SINLINE PRO 10000 series power supply units CONNECTING THE POWER SUPPLY UNIT Connecting elements Figure 4: Connecting elements with safeguards – safeguard of the service BYPASS line – primary line protection WEJ AC – input terminals – service BYPASS phase line –...
  • Page 27: Electrical System

    Instruction manual for SINLINE PRO 10000 series power supply units The system must be structured in such a way as to make possible the disconnection of the power supply unit from the mains, e.g. by the switching of integrated overcurrent cut-outs.
  • Page 28: Switching Off And Disconnecting The Power Supply Unit

    Instruction manual for SINLINE PRO 10000 series power supply units Once it has been correctly connected, start up the power supply unit by performing the following activities in the order mentioned: Check whether fuses F3 and F4 are OFF; if not, set them OFF.
  • Page 29: Operating Modes Of The Power Supply Unit

    Instruction manual for SINLINE PRO 10000 series power supply units OPERATING MODES OF THE POWER SUPPLY UNIT Figure 5: Graph presenting the operation modes of the power supply unit UNKNOWN mode An intermediate state that occurs when the power supply unit is started up following energisation.
  • Page 30: Other Functional Elements

    Instruction manual for SINLINE PRO 10000 series power supply units BACKUP mode (BATTERY OPERATION) If the primary power line does not satisfy the mains correctness criteria, the power supply unit switches to the BACKUP mode (battery operation mode). In BACKUP mode, the inverter supplies power to the battery outputs.
  • Page 31 Instruction manual for SINLINE PRO 10000 series power supply units mode) only when the overload falls below the set level (CONFIGURATION 3/4;ProgKas.Prz.). If in NORMAL operation mode the overload rises to 105%, the unit will start signalling this development by a continuous sound and the appropriate message on the display.
  • Page 32 Instruction manual for SINLINE PRO 10000 series power supply units Figure 7: Internal battery protection It is necessary to observe the instruction written in the frame below the fuses, namely that the fuses must be activated in the appropriate order. F1 should be activated first, and F2 10 sec.
  • Page 33: Avr

    Instruction manual for SINLINE PRO 10000 series power supply units The power supply unit is equipped with an AVR (Automatic Voltage Regulation) system that immediately corrects small drops (AVR - increasing) and rises in mains voltage, so as to ensure that receivers enjoy the proper supply conditions without using up the power gathered in batteries.
  • Page 34: Cooperation Of The Power Supply Unit With A Pc

    EVER SNMP/HTTP NETWORK MANAGEMENT CARD The EVER management card is optional and may be installed by the user. It serves to integrate the power supply unit with an Ethernet-based computer network. The network card is located in a special slot on the rear wall of the unit. The card allows the user to manage the unit from any computer in the network.
  • Page 35: Installing A Management Card

    Instruction manual for SINLINE PRO 10000 series power supply units Installing a management card Switch on the power supply unit by means of the user interface (CONTROL 1/3; UPS). Set safeguards F3 and F4 OFF. Switch off safeguards F1, F2 and F5 by opening the fusible cut-out mounts. The safeguards do not have to be switched off in any special order.
  • Page 36: Installing And Configuring Powersoft Personal

    Instruction manual for SINLINE PRO 10000 series power supply units INSTALLING AND CONFIGURING POWERSOFT PERSONAL Installing on a Windows system Before installing the PowerSoft software, you should: • uninstall your current version of PowerSoft and other monitoring software (if the user is replacing an emergency power supply unit that protects his PC), •...
  • Page 37: Updating Software

    Instruction manual for SINLINE PRO 10000 series power supply units rpm –ivh powersoftpersonal-x.x.x.i386.rpm Users working with the software must possess system administrator privileges (root) in order to install and subsequently use the programme. Following installation, the package is located in the catalogue /usr/local/powersoft.
  • Page 38: Comments Regarding Operation

    Instruction manual for SINLINE PRO 10000 series power supply units Linux/Unix systems PowerSoft software for systems from the Linux/Unix family may be updated using a new version of the package, downloaded from www.ever.eu. In the case of CentOS, RedHat, Suse Linux and Fedora Core systems, updates may be performed by means of the following command: rpm –Uv powersoftlite-x.x.x...
  • Page 39: Cooperation Of The Power Supply Unit With Electricity Generators

    The power supply unit should be stored and transported in accordance with the installation guidelines set forward in a separate document, attached to the device. If these requirements are not satisfied, EVER Sp. z o.o. shall not assume any liability for mechanical damage caused during transport.
  • Page 40: Technical Parameters

    Instruction manual for SINLINE PRO 10000 series power supply units TECHNICAL PARAMETERS INSTALLATION GUIDELINES PARAMETER \ POWER SUPPLY SINLINE PRO 10000 UNIT 10 kVA Apparent/active power 8 kW POWER SUPPLY PARAMETERS Power supply system topology 1P3W Rated voltage 230 V...
  • Page 41: Technical Data

    Instruction manual for SINLINE PRO 10000 series power supply units TECHNICAL DATA PARAMETERS SINLINE PRO 10000 10 kVA Output power 8 kW GENERAL DATA Topology Total efficiency for Pmax AC/AC > 98% Cooling Forced, internal fans Protection level IP20 Working environment...
  • Page 42: Information Concerning Legal Provisions And The Guarantee

    Apart from the provisions set forward in the guarantee card, EVER Sp. z o.o. does not provide any guarantees or warranties, including any guarantees of marketability or suitability for a specific application.