Service Functions - Mitsubishi Electric MSZ-GE22VA Service Manual

Hide thumbs Also See for MSZ-GE22VA:
Table of Contents

Advertisement

Mitsubishi ilmalämpöpumput huoltaa ja korjaa: Jäähdytinpalvelu RefGroup Oy
8

SERVICE FUNCTIONS

MSZ-GE22VA MSZ-GE25VA MSZ-GE35VA MSZ-GE42VA MSZ-GE50VA
8-1. TIMER SHORT MODE
For service, set time can be shortened by short circuit of JPG and JPS on the electronic control P.C. board.
The time will be shortened as follows. (Refer to 10-7.2.)
Set time: 1 minute → 1 second
Set time: 3 minutes → 3 seconds (It takes 3 minutes for the compressor to start operation. However, the starting time is
shortened by short circuit-of JPG and JPS.)
8-2. P.C. BOARD MODIFICATION FOR INDIVIDUAL OPERATION
A maximum of 4 indoor units with wireless remote controllers can be used in a room.
In this case, to operate each indoor unit individually by each remote controller, P.C. boards of remote controller must be
modified according to the number of the indoor unit.
How to modify the remote controller P.C. board
Remove batteries before modification.
The board has a print as shown below:
The P.C. board has the print "J1" and "J2". Solder "J1" and "J2" according to the number of indoor unit as shown in Table 1.
After modification, press the RESET button.
Table 1
1 unit operation
No. 1 unit
No modifi cation
No. 2 unit
No. 3 unit
No. 4 unit
How to set the remote controller exclusively for particular indoor unit
After you turn the breaker ON, the first remote controller that sends the signal to the indoor unit will be regarded as the remote
controller for the indoor unit.
The indoor unit will only accept the signal from the remote controller that has been assigned to the indoor unit once they are
set.
The setting will be cancelled if the breaker is turned OFF, or the power supply is shut down.
Please conduct the above setting once again after the power has restored.
J1
2 units operation
Same as at left
Solder J1
www.ilmalämpöpumput.com
J2
3 units operation
Same as at left
Same as at left
Solder J2
10
NOTE: For modification, take out
the batteries and press
the OPERATE/STOP (ON/
OFF) button twice or 3
times at first.
After modification, put back
the batteries then press the
RESET button.
4 units operation
Same as at left
Same as at left
Same as at left
Solder both J1 and J2