Fenwal DH-60 (2W) Manual

Fenwal DH-60 (2W) Manual

2-wire air duct smoke detector

Advertisement

Quick Links

2-Wire Air Duct Smoke
Detector
Models DH-60 (2W)
F-70.06
FEATURES
Approvals/Listing
UL 268A Listed File S1064
Factory Mutual Approved
CSFM Listed #3240-1076:121
NYC MEA Listed #134-95-E
City of Los Angeles Approved #RR8318
24 Vdc Operation
Connects to Fire Alarm Control Panel Initiating Cir-
cuit
Compatible with Fenwal Advanced Smoke Detectors
In-place Sensitivity Measurement (in % per foot
obscuration)
Remote Indication, Test and Reset Capabilities
Easily Mounts to Round or Rectangular Ducts
Wide Range of Duct Sizes and Air Velocities
Clear Lexan Cover for Easy Viewing of Smoke Detec-
tor Status and Cleanliness
DESCRIPTION
The Fenwal Series DH-60 (2W) Air Duct Smoke Detector
is designed for detecting particles of combustion in air
handling systems. The DH-60 (2W) Duct Detector hous-
ing accepts the Fenwal Advanced CPD-7054D Ionization
and PSD-7157D Photoelectric Smoke Detector Heads.
The DH-60 (2W) Detector connects to the Initiating Cir-
cuit of a UL Listed compatible Fire Alarm Control Panel
and upon detection of pre-set smoke levels, puts the
panel in a state of alarm. The panel may then control a
variety of devices, such as HVAC fans and dampers to
prevent the spread of smoke throughout the facility. A
transparent Lexan cover over the detection chamber
allows visual inspection of the duct detector's chamber
and the internal smoke detector status. Sampling is
accomplished by sampling tubes that extend into the
HVAC duct. Outputs provided can accommodate remote
alarm and power indication, remote test and remote
reset. Fenwal offers a range of remote accessories that
operate in conjunction with the duct detectors.
APPLICATION
The Fenwal Series DH-60 Duct Detectors are suited for
use with HVAC systems in commercial, industrial and
institutional fire alarm applications.
The DH-60 is easily mounted to both rectangular and
round ducts from 8 inches (200 mm) to 12 feet (3.6 m)
wide and is compatible with all ducts with air velocities
between 500 and 4000 feet per minute (2.5 to 20 m/s).
TM
Protection Systems
A UTC Fire & Security Company
The Ionization and Photoelectric Smoke Detector heads
listed above operate over this entire air velocity range.
SAMPLING TUBES
The operation of the DH-60 (2W) Duct Detector is based
upon an air sampling principle. Two tubes extend into the
HVAC duct to transport air from inside the duct into the
duct detector sensing chamber and back out to the duct.
If the sampled air contains a concentration of smoke
greater than or equal to the alarm threshold of the inter-
nal smoke detector, the unit will alarm. The duct detector
inlet supply sampling tube is selected according to the
size of the HVAC duct. A separate exhaust tube is not
required since an integral exhaust tube is molded into the
housing to simplify installation.
REMOTE INDICATORS/CONTROLS
A series of easily installed remote indicators are available
to add versatility and flexibility to the Fenwal Series DH-
60 (2W) Duct Detectors. These attractive and functional
devices provide convenient status information along with
remote Test/Reset capabilities. The remote indicators are
helpful when the detector is out of view or located in rela-
tively inaccessible locations. Figure 2 shows the face-
plates of the RA 911 and RA 914 remote indicator
controls.
FUNCTIONAL TESTING AND SENSITIVITY
MEASUREMENT
The Fenwal DH-60 (2W) Duct Detectors should be tested
upon installation and once a year thereafter as stated in
NFPA 72. All alarm signal devices, releasing devices,
and extinguishing systems, as applicable should be dis-
engaged before the test is performed and re-engaged at
the conclusion of testing.
Effective: May 2007
R

Advertisement

loading

Summary of Contents for Fenwal DH-60 (2W)

  • Page 1 Effective: May 2007 2-Wire Air Duct Smoke Detector Protection Systems Models DH-60 (2W) A UTC Fire & Security Company F-70.06 FEATURES • Approvals/Listing • UL 268A Listed File S1064 • Factory Mutual Approved • CSFM Listed #3240-1076:121 • NYC MEA Listed #134-95-E •...
  • Page 2 The DH-60 Duct Detector may be functionally tested either by introducing smoke into the detector or activating the magnet test. Two separate magnet-locating slots are provided on the outside of the duct detector housing. Further, as stated in NFPA 72, Detector sensitivity should be checked within one year of installation and every alter- native year thereafter.
  • Page 3 TECHNICAL SPECIFICATIONS Tables 1 and 2 list the technical specifications of the DH-60 (2W) Duct Detector. Table 1: DH-60 (2W) Input Voltage and Current Ratings Input Voltage Average Standby Maximum Standby Maximum Alarm Power Source Range Current Current Current 24 Vdc 10.2 - 36.8 PSD-7157D 55 mA 70 mA...
  • Page 4: Part Number

    Table 3: Ordering Information Part Number Model Description Duct Detector and Housings 70-600000-200 DH-60 (2W) 2-Wire Duct Housing less Detector with Integral Exhaust Tube 70-600000-257 DH-60-2APD DH-60 (2W) with Advanced Photoelectric Detector PSD-7157D 70-600000-254 DH-60-2ACD DH-60 (2W) with Advanced Ionization Detector CPD-7054D Duct Detector Sampling Tubes 06-129500-001 12 in.