CONTENTS SECTION TOPIC PAGE Introduction Important Features Product Line Safety Warnings Warranty Unpacking and Inspection Description of Operation Front and Back Panel Descriptions Electrical Specifications 10.0 Mechanical Dimensions of Shelves 11.0 Safety and Industry Standards 12.0 Operating Information 13.0 Parallel Operation 14.0 Installation and Testing 15.0...
Page 3
ILLUSTRATIONS FIGURE TITLE PAGE INV2500-HS and INV5000-HS Inverter Models Front & Back of INV2500-HS Module Front & Back of INV5000-HS System Mechanical Dimensions of INV5000-HS & INVR2U-HS Shelves INV2500-HS Inverter Output Waveforms INV2500-HS & INV5000-HS Overload Characteristic Connections for ORing Form C Relay Outputs on INV5000-HS...
Form C relay alarm contacts are available on the back. The units are self-cooled by internal fans. IMPORTANT FEATURES The following is a summary of the important features of the INV2500-HS and INV5000-HS inverters: Two Mounting Positions High: 3.5 Inches...
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL 5000VA Output for INV5000-HS 7VA per Cubic Inch Power Density 115VAC Output at 22 or 44 Amperes 230VAC Output at 22 Amperes Low Distortion 50 or 60Hz Sine Wave 42 to 56VDC Input Fully Isolated from Battery Input...
All products returned for repair must be shipped freight prepaid to UNIPOWER. If the buyer fails to fully comply with the foregoing, the buyer agrees that no other remedy (including, but not limited to, incidental or consequential damages for lost profits, lost sales, injury to person or property or any other incidental or consequential losses) shall be available to the buyer.
Figure 2 shows the front and back of an INV2500-HS inverter module. On the left side of the front panel of the INV2500-HS is the input circuit breaker. To the right are the two cooling fans and the output circuit breaker. Above the output breaker from the top are the green LED indicators for Input OK, Sync OK and Output OK.
OPERATING MANUAL INV2500-HS FRONT VIEW 3.32 (84.3) 8.50 ä (216) INV2500-HS BACK VIEW HOT-SWAP CONNECTOR Figure 2. Front and Back of INV2500-HS Module INV5000-HS FRONT VIEW A SIDE B SIDE 3.46 (87.9) DC INPUT AC OUTPUT DC INPUT AC OUTPUT...
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL or side B) of this inverter is a INV2500-HS. The back panel has a transparent plastic safety cover. The INVR2U-HS shelf with two INV2500-HS inverters in it is identical in appearance and dimensions to the INV5000-HS, both front and back.
Input conducted EMI meets FCC20780 part 15J Curve A and EN55022 Curve A. 11.4 Input voice band noise is less than 32dBrnC for a single INV2500-HS with a 240 ampere-hour battery or an INV5000-HS or two INV2500-HSs with a 480 ampere-hour battery.
INVR2U-HS are to bus bars with no. 1/4-20 studs. 12.2 Output Voltage. The output voltage for an INV2500-HS is 115VAC at full load, 120VAC at no load; for an INV5000-HS-230 it is 230VAC at full load, 240VAC at no load. See Figure 5(a). Frequency is 50 or 60Hz, ±0.1%. The output voltage has total harmonic distortion of less than 2.0%.
13.1 The INV2500-HS and INV5000-HS Series inverters are designed to operate in parallel for higher output current. For the INV2500-HS, the units are auto- matically connected in parallel in the INVR2U-HS shelf. The INV5000-HS 230VAC units have two INV2500-HS inverters connected in series in the shelf.
The following table shows output current and total volt-amperes for inverters connected in parallel. As mentioned earlier, INV5000-HS refers to both the 230VAC INV5000-HS-230 and two INV2500-HS inverters in an INVR2U-HS shelf producing 115VAC. Table 13-1. Output For Paralleled Inverters NO.OF INV5000-HS...
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL AC OUTPUTS Figure 9. Two 115VAC INVR2U-HSs in Parallel Using AC Distribution Panel INVR2U-HS INV5000-HS-230 Figure 10. Output Connections for Inverters...
INV2500-HS & INV5000-HS SERIES OPERATING MANUAL by means of the 1/4-20 studs. Connect the input ground (10-32 stud) to the system ground. Make sure the correct polarity is used and make sure the connections are clean and firm. Reversed input polarity could cause damage to the inverter.
16.3 When the INV2500-HS inverters are operated in a N+1 redundant mode, only the inverter module being replaced needs to be turned off as described in the following paragraphs. In this case it is true hot-swap replacement. If the...
Check battery voltage. Recharge battery or circuit breakers on. below range. install new battery. Turn the inverter back on. Input and Output OK LEDs off. 18.3 If none of the above actions solves the problem, call UNIPOWER Telecom at 954-346-2442 Ext. 400 for help.