Setup Procedures; Initial Setting - Panasonic KT2 Instruction Manual

Hide thumbs Also See for KT2:
Table of Contents

Advertisement

5. Setup procedures

5.1 Setup procedures
The setup procedures of this controller is shown below. Refer to each item for details.

(1) Initial setting

(2) Main setting mode: Set Step SV and Step time for Program control during Main setting mode.
(3) Sub setting mode : Set PID values, A1 value, etc during Sub setting mode.
(4) Auxiliary function setting mode 1: Set the Lock function, Communication conditions, etc. during
Run
5.2 Initial setting
Before using this controller, it is necessary to set up the Input type, Alarm type, Control action, etc.
according to the users' conditions. This is an initial setting.
Default values are set as follows.
Input: K –200 to 1370 , Alarm 1(A1): No alarm action, Alarm 2(A2): No alarm action, Reverse (Heating) action
If the users' specification is the same as the default value of the KT2, initial setting is not necessary.
Proceed to Section "6.1 Main setting mode".
Turn the power supply to the instrument on.
For approx. 3 seconds after the power is turned on, the MEMO/STEP display is turned off and the PV/SV
display indicates sensor input characters and temperature unit. (Table 5.2-1)
During this time, all outputs and LED indicators are in an OFF status.
After that, the following is indicated.
Basic operation for initial setting
Initial setting is conducted in Auxiliary function setting mode 2. To go to Auxiliary function setting mode 2,
press the
key for approx. 3 seconds while holding down the
Set or select the values with the
Pressing the
: Set the Input type, Alarm type, etc. during Auxiliary function setting mode 2.
(If the users' specification is the same as the default value of the KT2, initial
setting is not necessary for the controller.)
Refer to Chapter "6. Setup".
(If the users' PID values are the same as the default value of the KT2, it is not
necessary to set them.) Refer to Chapter "6. Setup".
Auxiliary function setting mode 1. (If the users' specification is the same as
the default value of the KT2, it is not necessary to set them.)
Refer to Chapter "6. Setup".
(Table 5.2-1)
Sensor input
K
J
R
S
B
E
T
N
PL-
C (W/Re5-26)
Pt100
JPt100
4 to 20mA DC
0 to 20mA DC
0 to 1V DC
0 to 5V DC
1 to 5V DC
0 to 10V DC
The MEMO/STEP display indicates a memory number. The PV/SV display indicates an
input value (e.g. room temperature). This is the PV/SV display mode.
or
key registers the values and goes to the next item.
PV/SV display
key.
8
key in the PV/SV display mode.