Setup; Main Setting Mode - Panasonic KT2 Instruction Manual

Hide thumbs Also See for KT2:
Table of Contents

Advertisement

6. Setup

6.1 Main setting mode

To go to the main setting mode, press the
Set each setting item with the
In the main setting mode, indicated setting items are different depending on the instrument status.
• Fixed value control
Setting items SV1 and SV2 will be indicated.
• Program control
Step SV and step time from Step 1 to Step 9 will be indicated.
Step number
200
C
0
C
(Fig.6.1-1)
Display
or
1
2
1:00
2:00
Program control run
SV1 (step 1 SV) setting
• Sets SV1 or step 1 SV.
• Scaling low limit value to Scaling high limit value
Step 1 time setting
• Sets step 1 time.
• Available only when program control function is selected during
OUT/OFF key function selection
• Setting range: 00:00 to 99:59
SV2 (step 2 SV) setting
• Sets SV2 or step 2 SV.
• Available when SV1/SV2 external selection function is
selected during DI (digital input) function selection or when
program control function is selected during OUT/OFF key
function selection.
• Scaling low limit value to Scaling high limit value
Step 2 time setting
• Sets step 2 time.
• Available only when program control function is selected during
OUT/OFF key function selection
• Setting range: 00:00 to 99:59
Step 3 SV setting
• Sets step 3 SV.
• Available only when program control function is selected during
OUT/OFF key function selection
• Scaling low limit value to Scaling high limit value
Step 3 time setting
• Sets step 3 time.
• Available only when program control function is selected during
OUT/OFF key function selection
• Setting range: 00:00 to 99:59
Step 4 SV setting
• Sets step 4 SV.
• Available only when program control function is selected during
OUT/OFF key function selection
• Scaling low limit value to Scaling high limit value
key in the PV/SV display mode.
key, and register the value with the
This program pattern shows that the
temperature rises to 200
and stays at 200
for 2 hours.
In this case,
Step 1 SV: 200
Step 1 time (1 hour): 01:00
Step 2 SV: 200
Step 2 time (2 hours): 02:00
Item, Function, Setting range
14
key.
for 1 hour
Default value
0
00:00
0
00:00
0
00:00
0

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents