User Mode - Produal HLS 44 User Manual

Versatile room controller
Table of Contents

Advertisement

WIRING
OPERATING AFTER A POWER FAILURE

USER MODE

Produal Oy
Keltakalliontie 18, 48770 Kotka FINLAND
 
Device connection and commissioning can only be carried out by qualified professionals.
Always make the connections while the power is switched off.
NOTE: The supply voltage potential must be the same in the controller and in the connected 24 Vac
actuators.
The maximum triac output current is 1 A. It is recommended to connect maximum of 4 thermal actuators
to the same controller output. The total current consumption must not exceed 1 A.
The triac outputs are protected with fuses that can only be changed by the manufacturer.
NOTE: Unused inputs and outputs can also be used for transferring other measuring and control
information over the Modbus.
The controller settings remain over the power failure.
Overdrives made over the Modbus are cleared during the power failure.
Tel: +358-5-230 9200 / Fax: +358-5-230 9210
USER GUIDE
A.
Indicator light
red = heating
o
green = cooling
o
B.
Display
temperature or set point
o
fan speed
o
C.
Set point change buttons
The set point changes in larger steps
when the buttons are quickly pressed
several times in a row.
D.
Fan speed control button
0 = STOP
o
1 = Speed 1
o
2 = Speed 2
o
3 = Speed 3
o
A = AUTO
o
E.
"Man in house" button
info@produal.fi
www.produal.com
HLS 44
2 (20)