ELECTRIC HEATER CONTROL

The controller can control an electric heater by using a solid state relay PR 50/440 between the A2 output and the heater. The relay must be
equipped with a PR 50Vac auxiliary card.
IMPORTANT: The controller is not equipped with a heater overheating protector. The overheating protection must be included in the heater
itself. The overheating alarm signal can be read by DI input, but the signal does not deactivate the heater control.
The overheating alarm signal can be connected to the DI1 or DI2 input, and the signal can then be read via the Modbus. DI input must be set
to "not in use" position (DI1mod = 0 or EXT.S = OFF).
Input
DI1
Overheating alarm
(x)
Note the following parameters:
Modbus
Parameter
Description
register
External temperature sensor / DI2
EXT.S
40009
contact input
DI2dir
28
DI2 operation direction (nc/no)
DI1mod
40021
DI1 mode
DI1dir
40022
DI1 operation direction (nc/no)
Produal Oy
Keltakalliontie 18, 48770 Kotka FINLAND
 
U1
S/DI2
(x)
factory
setting
OFF
1
0
0
Tel: +358-5-230 9200 / Fax: +358-5-230 9210
Output
Y1
Y2
Thermal actuator
24 Vac controlled solid
state relay
Min
Max
OFF=not in use, 1= external NTC sensor, 2=DI2 door/window contact (prevents
OFF
3
both heating and cooling), 3=DI2 condensation switch (prevents cooling)
0
1
0 = nc, 1 = no
0= not in use, 1= control to day mode with a nc/no switch connected to the DI1
0
1
input
0
1
in the night mode: 0 = nc, 1 = no