Malfunction Of Transmission Between Main And Sub Remote Controllers; Controllers - Panasonic U-4..6ML5XPQ Service Manual

Urban multi
Table of Contents

Advertisement

Panasonic
U8
3.46 "
"
Malfunction of Transmission between Main and Sub
Remote Controllers
U8
Remote
Controller
Display
Applicable
AII indoor unit models
Models
Method of
In case of controlling with 2-remote controller, check the system using microcomputer if signal
transmission between indoor unit and remote controller (main and sub) is normal.
Malfunction
Detection
Malfunction
Normal transmission does not continue for specified period.
Decision
Conditions
Supposed
Causes
Troubleshooting
Troubleshooting
Malfunction of transmission between main and sub remote controller
Connection between sub remote controllers
Defect of remote controller PC board
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Using 2-remote
controllers control.
YES
SS1
of both remote controllers is
set to "SUB."
YES
Troubleshooting by Indication on the Remote Controller
SS1
NO
of remote controller PC boards
is set to "MAIN."
YES
NO
NO
Set SS1 to "MAIN"; the
power supply off once and
then back on.
Turn the power off and then
back on. If a malfunction
occurs, replace the remote
controller PC board.
Set one remote controller to
"MAIN"; the power supply
off once and then back on.
(V2825)
197

Advertisement

Table of Contents
loading

This manual is also suitable for:

U-4..6ml5dpq

Table of Contents