Fault Finding - BENSON RS UHA Assembly And Use Manual

Gas fired room sealed unit heaters
Table of Contents

Advertisement

If heater is not working firstly check the following:
Check electrical supply
Check gas pressure
Check gas pressure is a stated in Technical Data
FAULT
No operation
No spark ignition.
Flue venter working
No indication lights on
No ignition
Flue venter not working
No indication lights on
Burner lights but cuts out
after 5 seconds
Explosive start up

FAULT FINDING

CAUSE
No electrical supply
Differential pressure switch not
working
Faulty differential pressure
switch
Poor connection at pressure
switch
Faulty flue venter
Faulty control box
Faulty ionization electrode
Room thermostat open
Faulty flue venter
Faulty control box
Phase and Neutral inverted
Faulty ionization probe
Faulty ignition
Faulty ignition electrode
Incorrect electrode position
Faulty burner tube
Faulty ignition transformer
37
SOLUTION
Check main isolator.
Check supply cables.
Check line fuses.
Check electrical connections
Check flue pipe and combustion
air pipe are clear
Replace differential pressure
switch
Check air pipes
Check electrical connection
Check that the air pipes are
condensate free
Change flue venter
Change control box
Check the electrode is not
cracked or damaged
Check the probe
Check room thermostat
Change flue venter
Change control box
Check
polarity
supply
Check electrical connection to
the probe.
Check probe
Change ionization probe.
Check that the gas type is
suitable for heater
Check gas pressure
Check head pressure.
Check gas supply pipes have
been purged of air.
Change ignition electrode
Reposition electrode correctly
over the burner bar
Change burner tube
Change transformer
of
electrical