INSTALLATION

________________________________________________
Your stove must be mounted on fireproof surface. If you have decided to mount it on an area
where flooring material is not fireproof, then you must add a panel of asbestos between the
stove and the floor. The thickness and dimensions of this panel differ according to each
model, as outlined in the following chart.
__________________________________________________________________________
Model
Thickness
of
panel
__________________________________________________________________________
Gemini 1200 3/8" (7mm)
__________________________________________________________________________
Gemini 1500 3/8" (7mm)
__________________________________________________________________________
Note: Asbestos panel can be replaced by a ceramic of gauge 18 sheet metal.
1) Whether you choose to install your stove cornerwise in a room or parallel to a wall, you
must adhere to the specifications for distances to be respected.
illustrated for each particular model.
Gemini 1200..............................................................................................................drawing #1
Gemini 1500..............................................................................................................drawing #1
2) Note : Only competent authorities can approve shorter distances.
3) Avoid placing wood or other inflammable substances too close to your heating unit. As
we have already stipulated, make sure that the proper distances are respected between
your unit and any inflammable substances.
Panel
Protrusion
at front
18" (457mm)
18" (457mm)
Panel
Protrusions
at sides
6" (150mm)
6" (150mm)
These are clearly
Panel
Protrusion
at back
6" (150mm)
6" (150mm)