Installer Setup; Temperature Settings - Honeywell T8602D Chronotherm IV Installation Instructions Manual

Deluxe programmable thermostats
Hide thumbs Also See for T8602D Chronotherm IV:
Table of Contents

Advertisement

Temperature Settings

Refer to Table 2 for the default program. If the daytime
energy savings period is not used, press the period key
(Leave or Return) until the time is blank. The fan setting
feature is available on select thermostat models. See
Owner's Guide, form number 69-0940, for complete
instructions on changing the program.
Table 2. Default Program Settings.
Period
Time
Wake
6:00 AM
Leave
8:00AM
Return
5:00 PM
Sleep
10:00 PM

INSTALLER SETUP

NOTE: For most applications, the thermostat factory-
settings do not require changing. Review
factory settings in Table 2 and if no changes are
necessary, go to the Installer Self-Test section.
The Installer Setup is used to customize the thermostat
to specific systems. Some of the options include
temperature display, changeover and outdoor
temperature display. Installer Setup numbers are listed in
Table 3. The table includes all the configuration options
and the factory settings for the T8602.
A combination of key presses are required to use the
Installer Setup feature:
— To enter the installer setup, press and hold the
information i key with the increase
decrease
keys until the first number is displayed.
All display segments appear for approximately three
seconds before the number is displayed. See Fig. 11
and 12.
— To advance to the next Installer Setup, press the
Time ∆ key.
— To change a setting, use the increase
decrease
key.
T8602D CHRONOTHERM
Heat
Cool
Setpoint
Setpoint
70°F
78°F
Auto
(21°C)
(25.5°C)
62°F
85°F
Auto
(16.5°C)
(29.5°C)
70°F
78°F
Auto
(21°C)
(25.5°C)
62°F
82°F
Auto
(16.5°C)
(28°C)
and
or
®
IV DELUXE PROGRAMMABLE THERMOSTATS
— To scroll the Installer Setup numbers backward, press
the Time ∇ key.
— To exit the Installer Setup, press Run Program.
Wait
Set Program
Recovery
Hold for
Filter
Em Ht
Mon
Tue Wed Thu Fri Sat Sun
Fan
Wake Leave Return Sleep
Setting
Fig. 11. Display of all LCD segments.
Fig. 12. Display of Installer Setup number and
CAUTION
Heat Pump and Electric Heat System
Configuration Hazard.
Can cause equipment damage.
Configure heat pump and electric heat systems to
1 in Installer Setup number 2 to prevent system
running without fan.
IMPORTANT
Only configurable numbers are shown on the
device. Example: If thermostat does not have a
system key, Installer Setup Number 12 will not
be displayed. Review Table 3 factory-settings
and mark any desired changes in the Actual
Setting column. When Installer Setup is com-
plete, review the settings to confirm that they
match the system.
5
Set Day/Time
Temporary Setting
AM
PM
Aux Ht
Days
Repl Batt
Room
Heat
DST
FACTORY SETTING OR OTHER
INSTALLER SETUP
CHOICE DISPLAY (COLUMN 3
NUMBER DISPLAY
OR 5 OF TABLE 3)
(COLUMN 2 OF TABLE 3)
setting.
System
Em Heat
Off
Cool
Auto
Fan
Outdoor
On
Cool
Auto
M14559