Extension Kit Installation

CAUTION
Secure the air intake hose and exhaust pipe with Pipe clamp B at intervals to
prevent contact between the air intake hose and the exhaust pipe.
If necessary, extension kits are available to extend the
exhaust line and air intake hose between the manifold
and the appliance.
(1) Maximum vent length allowed is 13 feet (4 m).
(2) Maximum vertical length allowed is 10 feet (3.0 m).
(3) Any length (horizontal and vertical) in excess of 10
feet (3.0 m) must be sloped 3° downward toward
the flue manifold to allow condensate to drain to
the outside.
(4) Do not allow any low points in the exhaust line
where condensate will collect.
These figures show the 3 possible ways that the ex-
tension exhaust line and air intake hose may be di-
rected away from the appliance. All 3 views are from
behind the appliance.
For your configuration, position the air intake hose
as shown.
Horizontal extension on left side
Plastic tie
V
r e
c i t
l a
e
x
e t
n
s
o i
n
o
n
right side
Rinnai Corporation ES17 / ES22 Manual
(5) Vent extensions installed in unconditioned air
space must be insulated with high temperature
insulation and must be accessible.
(6) Vent extensions must not be concealed per NFPA
54 and must be accessible allowing inspection and
repair. Decorative covers are available from
Rinnai.
V
r e
c i t
Plastic tie
l a
e
x
e t
n
s
o i
n
o
n
left side