8. Locate the capillary tube of the existing auto-
reset water temperature limit and remove it from the
strain relief clamp. See Figure 40.
Figure 40
INSTALLING THE NEW MANUAL-RESET WATER
TEMPERATURE LIMIT
1. Remove the cover from the reset button on the
new manual reset water temperature limit switch by
turning counter clockwise. See Figure 41.
2. In a similar manner, remove the locking nut from
the new manual reset water temperature limit. See
Figure 42.
3. Insert the manual reset push button of the water
temperature limit through the hole in the control
panel. See Figure 43.
Figure 41
Figure 43
Figure 42
18-CG01D1-4
33