Lennox FCM 85 Installation, Operating And Maintenance Manual page 47

Fcm/fhm/fgm/fdm/fwh/fwm series 85 > 234 kw air cooled and water cooled rooftop packaged units
Table of Contents

Advertisement

VENTILATION : AIRFLOW BALANCING
nd
2
method when adjusting the pulley :
-Close the pulley fully and count the number of turns
from fully closed position. Using table_1 determine the
motor pulley actual diameter.
-Record the fix fan pulley diameter.(DF)
-Determine the fan speed using the following formulae:
=
rpm
rpm
FAN
Where: rpm
:from the motor plate or table_2
MOTOR
D
: from table_1
M
D
: from machine
F
Once the pulleys are adjusted and the belt checked and
tensioned, start the fan motor and record the Amps and
Voltage between the phases:
Using the measured data and table_2
-Theoretical mechanical power at the fan shaft:
h
P
= P
x
meca fan
meca Motor
Transmission
h
P
= P
x
meca fan
elec
meca motor
= V x I x Ö3 x cosj x h
P
meca fan
This formula can be approximated in this way
P
= V x I x 1.73 x 0.78 x 0.87 x 0.9
meca fan
With the fan "rpm" and the mechanical power at the fan
shaft an operating point and the supplied airflow can be
estimated using the fan curves.
Table_3 Accessories pressure drops
G4
Filters
12000
1
85
15000
7
23000
28
14000
5
100
18500
15
23000
28
15000
7
120
20500
21
23000
28
18000
1
150
26000
12
35000
29
21000
5
170
30000
19
35000
29
24000
3
200
35000
18
43000
31
27000
7
39000
24
230
43000
31
FLEXYII_WSHP-IOM-1307-E
´
D
/D
MOTOR
M
F
h
x
Transmission
x h
meca motor
Transmission
UV
Hot
Hot
F7
LIGH
Water
Water
Filters
T
coil S
coil H
75
18
9
15
105
30
13
22
199
63
26
44
94
26
11
19
143
44
18
31
199
63
26
44
105
30
13
22
167
52
21
37
199
63
26
44
75
15
6
10
130
33
12
19
204
54
19
33
94
21
8
14
161
42
15
25
204
54
19
33
88
18
7
11
154
39
13
22
211
54
19
31
105
24
8
14
182
46
16
26
211
54
19
31
CHECKING AIRFLOW AND ESP
Using the fan curves on page 36 to 40, the airflow, the total
pressure available (P
pressure (Pd) can now be estimated, for a specific
operating point;
The next step consists in estimating the pressure losses
across the unit.
This can be achieved using the "dirty filter pressure sensor"
and the accessories pressure drop table: table_3
Also the pressure drop due to the duct inlet into the roof-top
unit can be taken as 20 to 30 Pa.
D
P
=
INT
Using the results from above, the external static pressure
(ESP) can then be estimated:
Table_ 2 Motor information
Motor Size
Nom. Speed
0.75 kW
1.1kW
1.5kW
2.2kW
3.0kW
4kW
5.5kW
7.5kW
9.0kW
11.0kW
Electric
Electric
Electric
Heating
Heater
Heater
Heater
Gaz
S
M
H
fired H
3
5
6
14
6
7
7
23
7
9
11
53
6
7
8
20
8
10
11
34
11
14
16
53
7
8
9
23
10
12
13
42
12
15
17
53
4
5
7
16
9
10
13
33
15
18
23
59
8
9
10
21
10
13
15
44
17
19
21
59
16
15
14
21
22
21
20
44
24
26
29
66
18
18
17
26
24
24
25
55
24
26
29
66
) and the corresponding dynamic
TOT
D
D
D
P
+
P
+
P
filter + coil
Inlet
D
ESP = P
- Pd -
P
TOT
INT
Cos j
1415 rpm
0,75
1435 rpm
0,78
1435 rpm
0,76
1450 rpm
0,78
1445 rpm
0,79
1445 rpm
0,75
1465 rpm
0,79
1460 rpm
0,79
1467 rpm
0,77
1460 rpm
0,79
Heat
Multidire
Adjustable
Recovery
ctional
roofcurb
Modul
Roofcurb
Fresh Air
17
22
164
27
33
204
63
73
313
23
30
191
41
51
252
63
78
313
27
35
204
50
62
279
63
78
313
30
35
170
62
72
245
112
131
329
40
49
198
82
95
282
112
131
329
53
67
173
112
133
252
169
195
310
67
84
195
139
163
281
169
195
310
Options
h
meca motor
79,9
83,7
84,2
87,1
85,7
86,7
89,0
89,1
90,9
90,4