Check Of R.v. Coil - Mitsubishi Electric MSH-18RV Service Manual

Split-type, heat pump air conditioners
Table of Contents

Advertisement

Check of outdoor unit
E
Compressor and / or outdoor fan motor doesn't stop.
1 Turn OFF the power supply.
2 After 30 seconds, turn ON the power supply again.
3 Operate the unit in COOL or HEAT mode by
pressing the EMERGENCY OPERATION switch.
4 Operate the unit for 1 minute or more and stop it by
pressing the EMERGENCY OPERATION switch again.
After 30 seconds,
does compressor stop?
After 30 seconds, does
outdoor fan motor stop?

Check of R.V. coil

F
Unit operates COOL mode even if it is set to HEAT mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Disconnect the TAB52 on the deicer P.C. board.
Turn ON the power supply and operate
the indoor unit in HEAT mode by pressing
the EMERGENCY OPERATION switch.
Unit operates HEAT mode even if it is set to COOL mode.
w First, measure the resistance of R.V. coil to confirm it is disconnected or is not short-circuit.
Disconnect the TAB52 on the deicer P.C. board.
Turn ON the power supply and operate
the indoor unit in COOL mode by pressing
the EMERGENCY OPERATION switch.
<MSH-24/30RV only>
Is there 220-240V AC
No
between A1-A2 on the
compressor contactor?
Yes
Ok
Replace the
deicer P.C. board.
No
Replace the
deicer P.C. board.
Yes
Ok
After 3 minutes, is there
220-240V AC between CN721
1-3 on the deicer P.C. board?
Yes
Replace the R.V. coil.
After 3 minutes, is there
220-240V AC between CN721
1-3 on the deicer P.C. board?
Yes
Replace the
deicer P.C. board.
Is there 220-240V AC
between 2/T1 on the
No
compressor contactor and N
on the outdoor terminal
block?
Yes
Replace the
compressor contactor.
No
Replace the
deicer P.C. board.
No
Replace the R.V. coil.
63
No
Make the connection
of wiring correct.
Yes