Temp-O-Matic TMP-105 Manual page 26

Oil furnace
Table of Contents

Advertisement

TMP
– Furnace Manual
Oil Furnaces
12 Dimensions and ratings
Model TMP-105, Burners data
BECKETT BURNER - Model AFG (3450 RPM) - Tube insertion 5 1/8"
Input
Firing rate
Model
BTU/h
70,000
TMP-105
88,200
105,000
RIELLO BURNER - Model 40-F3 - Tube insertion 5 3/16"
Input
Firing rate
Model
BTU/h
88,200
TMP-105
105,000
CARLIN BURNER - EZ-1 - Tube insertion 5 3/16"
Input
Firing rate
Model
BTU/h
70,000
TMP-105
88,200
105,000
Airflow data (CFM)
Model
Blower speed
Med-Low
TMP-105
Med-High
High
Notes :
Airflow values in cubic ft per minute (CFM) rounded to nearest 5 CFM.
Data taken with filters in place.
26
Nozzle
USGPH
(Delavan)
0.50
0.50 - 70A
0.63
0.50 - 70A
0.75
0.60 - 70B
Nozzle
USGPH
(Delavan)
0.63
0.50 - 60A
0.75
0.60 - 60A
Nozzle
USGPH
(Delavan)
0.50
0.50 - 60A
0.63
0.50 - 60A
0.75
0.60 - 60A
0.1
0.2
820
810
1115
1080
1435
1380
Pump
Low firing
pressure
Head
rate baffle
(PSIG)
100
F0
155
F0
155
F0
Pump
Combustion
pressure
air adjustment
(PSIG)
(Turbulator / Band)
155
0 / 3
155
0 / 4
Pump
Combustion
pressure
air adjustment
(PSIG)
(Bar / Band)
100
Bar # 0.50 / 0.50
155
Bar # 0.60 - 0.65 / 0.60
155
Bar # 0.75 / 0.75
External static pressure
0.3
0.4
795
785
1045
1010
1325
1270
Combustion
Static disc
air adjustment
(band/shutter)
Yes
2 3/4 #3383
Yes
2 3/4 #3383
No
2 3/4 #3383
0.5
0.6
770
760
970
935
1210
1155
0 / 4.5
0 / 8
0 / 7.5
0.7
750
900
1100
670-000-004/1010