RT9 Powershelf

5.3 Navigating MiniCSU-3 Functions

5.3.1 Base Menu (System Level Functions)

Home screen - FL indicates float mode and FLC indicates float mode with battery temperature compensation
25.2A 54.3V
FL
(↑)
DEC
INC
(If 1-ph AC Monitor not = Off)
(↓)
(If 3-ph AC Monitor not = Off)
(If Load Sensor not = Off)
158-1806-01.doc
Indicates that the front panel is locked. Press and hold ( ↑ ), ( ↓ ) and ENTER to unlock
Lock Panel
Press ENTER
Ambient temperature displayed in Degrees Centigrade
Ambient Temp
"Not Available" shown if not sensor is connected
28°C
Single phase AC voltage
1ph AC Volts
245V
Single phase AC current
1ph AC Current
52A
Single phase AC frequency
1ph AC Frequency
50Hz
Phase AC voltage
3ph AC1 Volts
245V
3ph AC2 Volts
243V
3ph AC3 Volts
246V
Phase AC current
3ph AC1 Current
28A
3ph AC2 Current
29A
3ph AC3 Current
32A
AC frequency
3ph AC Frequency
50.2Hz
ENTER
Volts High Alarm
Modify Value up/down
57.0V
ENTER to accept
ENTER
Volts Low Alarm
Modify Value up/down
49.0V
ENTER to accept
ENTER
Security
Modify Value up/down
Off
ENTER to accept
ENTER
Password Setup
Modify Value up/down
Press ENTER
ENTER to accept
Test Indicators
Press ENTER
ENTER
System Info
INC/DEC toggles system
Press ENTER
ENTER
System
Modify Value up/down
UPS
ENTER to accept
ENTER
Number of SMRs
Modify Value up/down
1
ENTER to accept
ENTER
Interface
Modify Value up/down
MUIB
ENTER to accept
ENTER
Num of Batteries
Modify Value up/down
1
ENTER to accept
ENTER
FS Batt Current
Modify Value up/down
20A
ENTER to accept
ENTER
Load Sensor
INC/DEC toggles state
Off
ENTER to accept
ENTER
FS Load Current
Modify Value up/down
100A
ENTER to accept
Bus voltage above which alarm flagged
Bus voltage below which alarm flagged
Programmable value change requires password when security on
Password programming submenu
Press ENTER to begin flashing display and LEDs
System information including controller software version, S/N and cabinet S/N
info
Options for "Standby" or "UPS" type system
Sets number of SMRs in the system
Selects the interface hardware to the system
Sets the number of batteries in the system
Sets full scale battery current
Sets full scale load current
29