C24/40/56/72; C24, C40, C56, And C72 Series - NAiS FP1 Hardware Manual

Fp series programmable controller
Table of Contents

Advertisement

2) C24, C40, C56, and C72 Series (Illustration: C72 series, AC type)
L
N
COM
BATTERY
100-240V AC
0
1
F.G.
-
24V DC
COM
0
2
4
+
(+) -
1
3
FP1-002-93-B
DIN Rail
Attachment Lever
RS232C Port (C24C, C40C, C56C, and C72C types only):
Use this connector to connect a peripheral device. [e.g., I.O.P.
(Intelligent Operating Panel), Bar-code reader and Serial printer, etc.]
Operation Monitor LEDs:
RUN LED
ON:
Flashes:
PROG. LED
ON:
ERR. LED
ON:
ALARM LED
ON:
Backup Battery Holder:
Refer to page 216, "7-3. Maintenance", for details about backup battery replacement.
Power Supply Terminals:
• AC type Control Unit: power supply terminals for 100 V AC to 240 V AC
• DC type Control Unit: power supply terminals for 24 V DC
Connector for Memory (EPROM) and Master Memory (EEPROM):
Use this connector to connect the Memory (EPROM) and the Master Memory (EEPROM).
Mode Selector:
RUN mode:
The Control Unit executes programs.
REMOTE mode:
The mode (RUN mode or PROG. mode) can be changed using programming
tools (e.g., FP Programmer II and personal computer with NPST-GR Software).
PROG. mode:
You can edit a program.
COM
COM
COM
COM
COM
COM
COM
COM
9
B
D
F
COM
2
3
4
5
6
7
8
A
C
E
0
min.
max.
RUN
RUN
REMOTE
V0
PROG.
PROG.
ERR.
min.
max.
0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3
ALARM
V1
min.
max.
V2
0
1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3 4 5 6 7 8 9 A B C D E F 0 1 2 3
min.
max.
V3
6
COM
8
A
C
E
COM
0
2
4
6
COM
8
5
7
(+) -
9
B
D
F
(+) -
1
3
5
7
(+) -
Input Terminals:
C24 series: 16 points, C40 series: 24 points, C56 series: 32 points,
C72 series: 40 points
Input voltage range: 12V DC to 24 V DC
This terminal block is removable with screws at both ends.
Terminals marked with "•" cannot be used as input terminals.
Built-in DC Power Output Terminals for Inputs (AC type only):
DC power for inputs can be supplied from these terminals. See page 45.
Programming Tools Connector (RS422 port):
Use this connector to connect the programming tools (e.g., FP Programmer II or personal
computer with NPST-GR Software) using the FP1 Peripheral Cable.
Baud Rate Selector:
Selects the baud rate for communication with a peripheral device (FP Programmer,
FP Programmer II or personal computer with NPST-GR Software).
Sets the baud rate selector according to the peripheral device to be connected to the RS422 port.
FP Programmer (AFP1112):
FP Programmer (AFP1112A):
FP Programmer II (AFP1114):
Personal computer with NPST-GR:
Potentiometers (V0 to V3):
Set with a screwdriver, the potentiometers allow you to manually adjust the controller.
This feature lets you input an analog value ranging from 0 to 255.
Each set value is stored respectively in manual dial-set registers (V0: DT9040, V1: DT9041,
V2: DT9042 and V3: DT9043).
C24 series: 2 (V0 and V1); C40, C56, and C72 series: 4 (V0 to V3)
when program is executed
when forcing input/output is executed in RUN mode
when the Control Unit halts program execution
when a self-diagnostic error occurs
when an abnormality is detected or watchdog timer error occurs
Output Terminals:
C24 series: 8 points, C40 series: 16 points, C56 series: 24 points,
C72 series: 32 points
This terminal block is removable with screws at both ends.
Terminals marked with "•" cannot be used as output terminals.
1
3
COM
5
7
COM
9
B
D
F
2
4
6
8
A
C
E
A
C
E
COM
0
2
4
6
9
B
D
F
(+) -
1
3
5
7
DIN Rail Attachment Lever
19,200 bps
19,200 bps or 9,600 bps
19,200 bps or 9,600 bps
9,600 bps
2-1. Parts Terminology and Functions
2-1. Parts Terminology and Functions
I/O Name Board
I/O State Indicators:
Indicates the input and output
ON/OFF states.
Expansion Connector:
Connects to the FP1 Expansion
Unit or FP1 Intelligent Unit
(FP1 A/D Converter Unit or FP1
D/A Converter Unit) or FP1 I/O
Link Unit.
See page 12 and 42.
23