Over Heat Of Compressor; Error Of Signal Transmission - Mitsubishi Heavy Industries SRK20ZGX-S Technical Manual

Inverter wall mounted type room air-conditioner ( split system, air to air heat pump type )
Hide thumbs Also See for SRK20ZGX-S:
Table of Contents

Advertisement

Over heat of compressor

Is discharge pipe sensor
resistance value good?
Is sufficient quantity of refrigerant
circulated?

Error of signal transmission

Does error persist after power
reset?
Is there any wrong connection on
indoor/outdoor unit wiring?
Is DC 0~Approx. 12V detected
between 2~3 terminals on
indoor unit terminal block?
Is DC 0~Approx. 12V detected
between2~3 terminals on
outdoor unit terminal block?
Is AC 220/230/240V applied
between 1~2 on the outdoor side
terminal block?
Is there any problem on the power
supply line (fuse, reactor,
capacitor, etc.)?
(page 41)
YES
YES
Defective inverter
YES
YES
YES
YES
YES
YES
Defective outdoor unit PCB
Connector connection check, resistance
NO
value check, replacement of discharge pipe
sensor
NO
Does trouble persist after
charging gas?
YES
Clogged capillary tube or
strainer, defective EEV, etc.
[Wiring error including power cable, defective indoor/
outdoor unit PCB, error on power supply system]
NO
Trouble by transient cause, not unit trouble.
NO
Correct improper wire connection on indoor/
outdoor unit.
NO
Defective indoor unit PCB
NO
Check crossover wires.
NO
Defective indoor unit PCB. Check crossover wires.
NO
Replace fuse, reactor or capacitor.
43
-
-
[Gas shortage, defective discharge
pipe sensor]
NO
Check if there are any
places where gas is leaking.