Installation; Instructions For The Fitter; Specifications - Gira 0394 Series Installation Instructions

Up underfloor heating thermostat

Advertisement

GIRA
UP Underfloor Heating Thermostat
Info
Installation Instructions
3.

Installation

3.1 Control Device: on a commercially available concealed socket, Ø 55.
Caution! The device should always be installed with its retaining ring on top of the wallpaper.
a) Remove housing cover. Pull off setting knob. Loosen lid screw. Remove lid.
b) Electrical supply: in accordance with circuit diagram; solid conductor-section 1 to 2,5 mm². No
earth lead required. Earth lead terminals is only used for looping through.
When mounted properly, the requirements of protection class II are fulfilled.
c) Fit the thermostat on to the socket using a thread-moulding Flush mounted socket screw.
d) Put on housing lid. To do this, the lid must slot into the top left of the housing base.
e) Continue as under a) but in the opposite direction.
3.2 Sensor:
The sensor must fulfil the requirements of protection class II and absolutely must be laid in a protective
tube, together with sensor cable H03VV. In this way, the sensor is protected from damp and can easily
be replaced in the event of repair.
4.

Instructions for the Fitter

The I-O switch on the control device is a single-pole switch disconnecting the device from the
mains and interrupting the electric circuit to the heating resistor in the floor.
For work on the load circuit, the power supply must at all times be disconnected. e.g. the fuse
removed.
The relay contact is closed when the sensor is disconnected, when the sensor is short-circuit, the
relay contact is open.
Caution!
In the event of a fault, electric potential may be present at the sensor.
5.

Specifications

5.1 Control Device:
Order reference
Operating voltage
Permissible variation
Temperature range (number scale)
Switching current at AC 250 V
Breaking capacity
Rated surge voltage
Switch
Red LED indicator
Green LED indicator
Contact (relay)
Temperature reduction (TA)
Switching temperature difference
Protective system conformity with EN 60529
Operating temperature
Storage temperature
UP Underfloor Heating Thermostat
0394 ..
AC 230 V 50 Hz
AC 195...253 V 50 Hz
, 2, 3, 4, 5 (= 10...50° C)
10 (4) A cos ϕ= 1
2,3 kW
4,000 V
Mains, "On/Off"
Control device demands heat (heating operation)
Temperature reduction "ON"
1 make contact (for heating) (not floating)
approx. 5 K
approx. 1 K
housing in IP 20
T 40
-25 T 70
12/13
Page 2 of 5