203GT is a new generation heating regulator.
Its versatility, intelligence and clarity have made it
an ideal heating regulator for all kinds of water
circulation heating systems.
In addition to heating control, 203GT has a
number of other control and alarm functions
for facilities.
Measurement information can be read, settings
and controls can be checked and adjusted,
and alarms can be received and acknowledged
remotely via a GSM telephone's text messages.
A GSM modem (optional equipment) must be
connected to 203GT to enable GSM use.
User manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 203GT and is the answer not in the manual?

Questions and answers

Summary of Contents for Lampoassa 203GT

  • Page 1 Its versatility, intelligence and clarity have made it an ideal heating regulator for all kinds of water circulation heating systems. In addition to heating control, 203GT has a number of other control and alarm functions for facilities. Measurement information can be read, settings...
  • Page 2 Remote control options: Remote control via a GSM phone Most of 203GT’s user level functions can also be carried out via GSM phone text messages. Text message use is illustrated on page 18.
  • Page 3: Table Of Contents

    CONTENTS User guide Settings for characteristic heating curve Settings Measurements Measurements and sensor connection information Supply water temperature information Operating modes Clock functions Language selection Type information Start function Alarms GSM functions Maintenance guide These pages contain Entering the maintenance mode directions for maintenance Tuning values persons.
  • Page 4 1. outdoor temperature of -20 C 2. outdoor temperature of 3. outdoor temperature of +20 C 203GT prevents the setting of an incorrectly shaped charac- teristic heating curve. It automatically suggests an adjustment. OPERATING INSTRUCTION: Press until the display no longer changes.
  • Page 5 Houses with floor heating Set the 203GT regulator's maximum limit between +35 ... +40 C and the minimum limit between +20 ... +25 C. In floor heating solutions it is important to make sure that exessively hot water which could damage structures or surfaces doesn't ever get into the network.
  • Page 6 SETTINGS Ajan asetus Browsing, making changes In 203GT the regulator is controlled by many different settings. Settings are selected according to sensor connections and geothermal heating selection (is it full effect or limited effect geothermal heating in use, see page p. 24).
  • Page 7 Additional information about settings Ajan asetus Settings: Factory Explanation: Attention! Range: Settings Room compens. Room sensor (TMR) 1.5 °C 0.0...7.0°C Room compensation ratio: If the room must be connected temperature is different than what it is set at, (H1:meas.3, the room compensation corrects the supply H2:meas.
  • Page 8: Settings

    Additional information about settings Ajan asetus Settings: Factory Explanation: Attention! Range: Settings Full effect geothermal heating (see also p. 25-26). Temperature setting of measurement 9. A compressor running Accumulator's 55°C 5...55°C command is given when the temperature of the accumulator's upper upper part min.
  • Page 9: Measurements

    MEASUREMENTS Labeling The regulator can be connected to 14 different measurement data at the same time (11 NTC measurements + 3 digital inputs).Measurement data can also be read through the bus. Also the position of the voltage controlled (0...10V or 2...10V) actuator can be seen. Measurements 6 and 11 can be used to indicate external alarms (additional information on alarms page 17) ATTENTION! Only the measurements connected to the regulator appear on the display.
  • Page 10: H1 Room

    MEASUREMENTS Additional information Strip con- Measure- Measurement information: Setting Attention! nector ment: range: Out temp Outdoor temperature -50...+50 Can be read through the net 2 H1 Supply Supply water temperature in regulating circuit H1 0...+130 3 H1 Room Room temp. in regulating circuit H1 (room comp.) -10...+80 Can be read through the net 5 H2 Supply...
  • Page 11 SUPPLY WATER INFORMATION In this mode we can see which factors determined by the regulator make up the supply water temperature at the time of inspection. The basis for this is the supply water temperature at the present outdoor temperature according to the characteristic heating curve. OPERATING INSTRUCTION: Automaattiohj Automaattiohj...
  • Page 12: Operating Modes

    OPERATING MODES Each regulating circuit can be controlled with the operating modes mentioned below. The factory set automatic regulation is a normal regulating situation in which the clock controlled temperature drops are also possible. The selected operating mode always appears on the basic display on the top line.
  • Page 13: Clock Functions

    23/08 da/mo The weekday blinks. Use the or button to set the weekday. Press 2007 Thursday Exit with ESC. Attention! The 203GT regulator's clock registers summer time and standard time changes and leap years. The battery lasts approx. 10 years.
  • Page 14 Clock programs - browsing, adding, deleting With the freely programmable 24 hour/7 day clock you can drop the temp. for certain lengths of time (heat. circuits H1 and H2) OPERATING INSTRUCTION: Automatic Press until the display no longer changes. Outdoor °C You are then in the "Selection"...
  • Page 15: Type Information

    LANGUAGE/KEEL The 203GT regulator is in two languages. The regulator has the most commonly used languages Finnish - Swedish or English - Eesti. The language of the regulator can be changed in the following manner: OPERATING INSTRUCTION: Press until the display no longer changes.
  • Page 16: Start Function

    START FUNCTION Regulat. mode sel. In the start function the regulator detects the sensors that are attached to it. The regulator takes the regulating circuits (H1, H2 and HW) into use according to the supply water sensors. The assumption is that there is a basic regulator in each regulating circuit.
  • Page 17: Alarms

    ALARMS! 203GT gives an alarm when a situation deviates from the norm. In the event of an alarm, the controller gives an alarm and an alarm message appears on the display. Also, the alarm relay contact closes. Note! Although the cause of the alarm has disappeared, the last alarm remains permanently on the display until it is acknowledged.
  • Page 18: Gsm Functions

    GSM-FUNCTIONS A GSM modem can be connected to 203GT, making it possible for the user to communicate with the controller via GSM phone text messages. (installation p. 37). A GSM phone can be used to carry out most of the user level functions in this manual, e.g., measurements, settings, heating curve settings, supply water info and the...
  • Page 19: Entering The Maintenance Mode

    ENTERING THE MAINTEN. MODE Access to the Ouman EH-203/GT maintenance mode is prevented by user rights. Only those persons who have a maintenance code have access to the maintenance mode. There are typical tuning values and settings in the maintenance mode which the maintenance person needs in conjunction with installation.
  • Page 20: Tuning Values

    TUNING VALUES 203GT has three PID regulators. The tuning values may have to be adjusted, for example, when the geothermal heating is installed if the setting wavers with the original factory setting. Anticipate and quick run can be set in the HW regulating circuit in addition to PID.
  • Page 21: Settings

    SETTINGS 203GT has three types of settings: user level settings which the user can adjust (p. 6-8) maintenance mode settings which the maintenance person may have to adjust special maintenance mode settings which seldom have to be adjusted (p. 30) Directions for entering the The original factory settings are restored in special maintenance (p.
  • Page 22: Trends

    TRENDS It is possible to follow supply water temperature changes on the trend Directions for entering the display with the graphic depictor. You can decide yourself how often the maintenance mode are on page 19. temperature is measured. The factory set sampling interval is 1 second. H1 Maint mode Press the button to move the cursor to “Trends”.
  • Page 23: Actuator Selection

    ACTUATOR SELECTION The control mode for each regulating circuit actuator is selected in actuator selection. Options are either 24 VAC 3-point control or DC voltage control (0...10V or 2...10V). Regulating circuit H1 actuator's control output is M1. Regulating circuit H2 actuator's control output is M2. Directions for entering the Regulating circuit HW actuator's control output is M3.
  • Page 24: Geothermal Heating

    GEOTHERMAL HEATING Select full effect or limited effect geothermal heating. After this selection you can change the settings that switch the compressor and electrical heating resistor on and off. Relay 1 controls the geothermal heating unit's electrical heating resistor and relay 2 controls the running of the geothermal heating unit's compressor.
  • Page 25 Full effect geothermal heating There are two heating circuits (H1 and H2) and one domestic hot water regulating circuit (HW) in the203GT. Relay 1 Geothermal heating unit's electrical heating resistor control. When relay is inactive, the electrical heating electrical resistor is switched on (strip connector 73- heating resistor...
  • Page 26 Full effect geothermal heating Alarms: The ”Electric heat” alarm goes off when the electrical heating resistor switches on (10s delay) . Measurement 4: If the controller has given the compressor a running permit but measurements does not receive running information, a ”CompressorRun” deviation alarm is given and the controller deletes the compressor's running permit. The compressor tries to restart after 5 minutes and after that at 60 minute intervals if the electrical heating resistor is not on.
  • Page 27 Limited effect geothermal heating There are two heating circuits (H1 and H2) and one domestic hot water regulating circuit (HW) in the 203GT. Relay 1 Geothermal heating unit's electrical heating resistor control. When relay is inactive, the electrical heating resistor is...
  • Page 28 Limited effect geothermal heating Alarms: Measurement 4 : If the controller has given the compressor a running permit but measurements does not receive running information, a ”CompressorRun” deviation alarm is given and the controller deletes the compressor's running permit. The compressor tries to restart after 5 minutes and after that at 60 minute intervals if the electrical heating resistor is not on.
  • Page 29: Restore Factory Settings

    RESTORING SETTING Restoring settings: 1. The regul. restores factory settings to the charasteristic heating curve settings. 2. Eliminates clock functions 3. Restores user and maintenance level settings 4. Selects automatic control for the operating mode 5. Selects the basic regulator for the regulator type. 6.
  • Page 30: Settings

    SETTINGS In the 203GT heating regulator the user can adjust most of the settings (see settings p. 6-8). Some of the settings that control the regulator's functions can be set in the maintenance mode (see page 21) and some in special maintenance. Seldom needed settings can be Directions for entering the adjusted in special maintenance.
  • Page 31: Measurement 6 Setting

    MEASUREMENT 6 SETTING In this special maintenance mode, measurement 6 can be changed from just a free temperature measurement to a regulating circuit H2 room compensation measurement or a regulating circuit H1 and H2 wind or sun compensation measurement. Free temperature measurement Directions for entering the is a factory setting which is labeled "Measure 6".
  • Page 32 68 % table. 76 % 70 % 84 % 80 % 92 % 90 % 100 % 100 % Wind or sun sensor connection: 203GT 203GT Measurement Measurement Add series shunt shunt resistor resistor 0 - 20 mA 24 VAC...
  • Page 33: Measurement 11 Setting

    MEASUREMENT 11 SETTING The value of measurement 11 can be changed in this special maintenance mode. ”Hot gas” is a factory setting. Directions for entering the maintenance mode are on page 19. Erikoishuolto Aset.palautus Special mainten. Asetusarvot Rstore settings Press the button to move the cursor to "Meas.
  • Page 34: Digital Inputs

    DIGITAL INPUTS 203GT has three digital inputs. A digital input can be connected to contact information or pulse information. Contact information can be used to receive an alarm. Alarms can be labelled using the text editor according to their cause. Alarms can be transferred to, e.g., A GSM phone as text messages.
  • Page 35: Lon Initialization

    NET CONNECTIONS/ LON initialization 203GT controller can be connected to the MODBUS, RS-485 or LON bus. When the EH-203/GT controller is connected to the bus, a (Modbus-200, EH-485, or LON-200 card) bus adapter card (optional equipment) is installed. Detailed instructions for installing and initializing the bus adapter card are provided.
  • Page 36 NET MEASUREMENT 203GT has an LON-200, RS-485 and MODBUS-200 bus adapter cards as an optional equipment. In this special maintenance mode you can select which measurement informati is to be read from the net. If you selected to read wind or sun measurements from the net, you must set the compensation area in this mode.
  • Page 37 The power is on but the modem is not ready to use. Inspect the following: 1. 203GT has the same PIN code as the GSM modem's SIM card PIN code. 2. Perform the start-up function. To start-up, move to Start function. Press OK. Exit with ESC without changing settings.
  • Page 38: Net Measurements

    RS-485 field bus through the master device, EH-686. An EH-485 bus adapter card must be installed in the controller so that the 203GT controller can be connected to the RS-485 field bus. (see installation and initialization guide in the instructions that come with the EH- 485 card).
  • Page 39: Direct Computer Connection

    Direct computer connection The 203GT regulator can be connected directly to a computer. DATAJAMAK cable is used to make the connection. Attention! If there are interferences in data transfer, try connecting the cable cover to the D-25 connnection pin no. 1 (protective GND).
  • Page 40: Installation And Maintenance Guide

    INSTALLATION AND MAINTENANCE GUIDE 203GT is fastened to its mounting base with three screws (two Changing the fuse: mounting points under the cover in the connection space and one in the installation bracket. Cables can be brought for the regulator from above (standard factory delivery) or from below.
  • Page 41 GENERAL CONNECTION DIAGRAM Modem connection 203GT heating regulator Cabling Field apparatus Modem connecting cable Jumper DATAJAMAK EIA-232 RX wire 2x(2+1)x0,24 EIA-232 GND connection If the modem is connected to the RS-485 bus, see Connection in the EIA-232 TX instructions that come with the RS-485 card.
  • Page 42 OPTIONAL EQUIPMENT LON-200 LON -200 is an adapter card which changes the 203GT regulators' serial communication bus so it is compatible with the LON field bus. An installation guide comes with the LON-200 adapter card. EH-485 Ouman has an EH-485 bus adapter card available as optional equipment which makes the 203GL serial interface compatible with the RS-485 field bus.
  • Page 43 INDEX Heating curve setting 4, 5 Accum. lower part min limit 7, 24-28 Relay controls 24-28 Accum. lower part temp. hyst. 24-28 Heating resistor control 24-28 Restoring settings 29 Heating resistor's hysteresis24,27,28 Accum. temperature 24-28 Room compensation 6, 31, 32, 36 Home/away switch 34, 6 Accum.
  • Page 44 Technical information: Operat. voltage: 230 VAC, 50 Hz, 0.20 A Digital inputs: 3 pieces The potential free contact is Casing: PC/ ABS connected to the digital input (load 6...9 VDC/20 mA) Protection class: Without cover seal IP 41 Outputs: 3 actuator control outputs 3- point 24 VAC or voltage control (0...10 V or 2...10 V) Actuator's Measurements...