LÄMPÖÄSSÄ
Vmi 6 – 17
INSTRUCTIONS FOR USE,
INSTALLATION AND
MAINTENANCE
LÄMPÖÄSSÄ 3/2016

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VMI 6-17 and is the answer not in the manual?

Questions and answers

Summary of Contents for Lampoassa VMI 6-17

  • Page 1 LÄMPÖÄSSÄ Vmi 6 – 17 INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE LÄMPÖÄSSÄ 3/2016...
  • Page 2 100% GEOTHERMAL HEAT Foreword We thank you for your confidence in our products and congratu- late you on making an excellent choice! You have selected a long- lasting and environmentally friendly Lämpöässä geothermal heat system. We hope that you will enjoy the trouble-free heating pro- vided by Lämpöässä...
  • Page 3: Table Of Contents

    Contens USER MANUAL INSTALLER MANUAL 4. INSTALLATION WORKS 1. Safety 4.1. Before installation 2. Geothermal heating system operation 4.1.1. Transport 2.1 Lämpöässä Vmi structure and operating principle 4.1.2. Ground source heat pump installation area 2.1.1. Heat collection circuit 4.1.3. Removing the packaging 2.1.2.
  • Page 4: User Manual

    100% GEOTHERMAL HEAT USER MANUAL 1. Safety In order to ensure trouble-free operation of the Lämpöässä geothermal Press this button for additional information on the touch heating system and achieve the best efficiency, the system must be screen data. transported and installed in accordance with the manufacturer’s instruc- tions.
  • Page 5: Lämpöässä Vmi Structure And Operating Principle

    USER MANUAL 2.1 Lämpöässä Vmi structure and operating principle 2.1.2. Compressor unit The Lämpöässä Vmi is especially suitable for use as the primary heating From the evaporator, refrigerant vapour is transferred to COMPRESSOR system of new and renovated residential buildings and secondary resi- (2) for ramping up the pressure.
  • Page 6: Ässäcooling Cooling System

    100% GEOTHERMAL HEAT USER MANUAL heated by using superheat removal heat exchanger (superheater 3) by installed cooling connections rendering installation effortless. The cool- the extremely high thermal energy acquired from the compressor. Hot ing connections are equipped with plugs; one of them is provided with a superheating energy is stored for final heating of domestic hot water.
  • Page 7: Touch Screen Functioning

    USER MANUAL These instructions contain a user manual and a manual for equipment Use the button in the bottom left corner to return to the home screen. installer. Maintenance functions are password-protected. Use the arrow button in the bottom right corner to return to previous screen.
  • Page 8: Room Temperature Adjustment By Room Temperature Measurement (Optional Equipment)

    100% GEOTHERMAL HEAT USER MANUAL 3.4.2. Room temperature adjustment by room tempera- 3.4.3. Domestic water boost ture measurement (optional equipment) The storage tank can be set to function at maximum thermal output in As an option, the room temperature measurement function can be order to meet transient needs, for example, if the need for domestic hot acquired for the system.
  • Page 9: Measurements

    USER MANUAL 3.4.6. Timer functions Set the desired heat distribution circuit temperature adjustment under Room temperature adjustment; values between -10...+10 °C are possi- ble. Set the desired storage tank temperature adjustment value under Timer functions can be utilised, for example, in secondary residences or Storage tank temperature adjustment.
  • Page 10: Adjustment Curves

    100% GEOTHERMAL HEAT USER MANUAL 3.4.9. Optional equipment This shortcut allows accessing the Optional equipment menu, which will be discussed in more detail in the chapter on menu functions. The last timing column consists of symbols describing the state of timing. A white symbol means that there is no active timer setting for the weekday.
  • Page 11: Adjustment Curves

    USER MANUAL pumps and 60 °C (bottom section) / 85 °C (top section) in case of part- water-related hazards. In general, the compressor is controlled according power geothermal heat pumps. to the minimum setting of the storage tank lower part. The value Correction indicates the temperature as corrected by the Timer In summer, when there is no need for heating (with the exception of function, Home/Away function, Domestic water boost function, or auto-...
  • Page 12: Other Set Values

    100% GEOTHERMAL HEAT USER MANUAL 3.5.3.1. Language For the temperature correction caused by Home/Away or Timer functions, see the bottommost line. The Language menu allows choosing between Finnish, Swedish and English for the user interface language. Maximum domestic water temperature can be limited by adjusting the Domestic water temperature limit value between 0...90 °C (factory set- 3.5.3.2.
  • Page 13 USER MANUAL 3.5.3.6. Summer functions Factory settings for heat distribution circuits are as follows: Set value and Meaning Factory This screen allows stopping of the heat distribution circuit water circula- setting range setting tion pumps during the summer to save energy. Supply water1 Maximum value of heat distribution 60 °C...
  • Page 14: Measurements

    100% GEOTHERMAL HEAT USER MANUAL (heating/cooling/turned off) is informed. External control When controlling method is external cooling is controlled by external ther- mostat which to be connected according the electrical drawing. Manual control When controlling method is manual can cooling be activated in this screen. 3.5.5.
  • Page 15: Installer Manual

    INSTALLER MANUAL 4. INSTALLATION WORKS that, remove the wooden platform elements and their fixation screws (4 pc). To remove the platform, lift the equipment by a fork lift, for 4.1. Before installation example. Pipe assemblies for the installation of the Lämpöässä system may only be 4.1.2.
  • Page 16: Space Requirements

    100% GEOTHERMAL HEAT INSTALLER MANUAL 4.1.4. Space requirements 4.2.2. Filling and de-aeration of the heat collection circuit A Lämpöässä Vmi ground source heat pump can conveniently be placed Accessories required for the filling and de-aeration of the ground circuit: into a technical or utility room. The floor space to be reserved for the •...
  • Page 17: Heating And Domestic Hot Water Connections

    INSTALLER MANUAL 10. When de-aeration has been completed turn the motor protection Heating connection switch QM1 off and also manual control function off. 11. Open shut-off valve (1) at the back of the group of fill valves. Heat distribution circuit surface sensors located on top of the storage tank 12.
  • Page 18: Hvac Checklist

    100% GEOTHERMAL HEAT INSTALLER MANUAL The storage tank is to be filled with special care through the group of fill funnel if the distance to the floor drain is more than two metres. The valves included in the system so that the storage tank pressure never overflow funnel must be directed down towards the floor drain.
  • Page 19: Electrical Installation And Outdoor Sensors

    INSTALLER MANUAL • the heating system has been filled and de-aerated appropriately 4.3.2. Room sensor (optional) • the ground circuit has been installed, filled and de-aerated In order for the room sensor to detect average indoor temperatures as appropriately reliably as possible, it must be placed in a central and open location, for 4.3.
  • Page 20: Electrician's Checklist

    100% GEOTHERMAL HEAT INSTALLER MANUAL • External supply is connected to terminals A1 and A2. Possible problems during startup • Terminals 15 and 16 are connected to geothermal heat pump and interrupt the heating element’s supply with respect to the phase the current value of which is exceeded.
  • Page 21: Maintenance Manual

    No text is visible on The device is not getting Check that that the control the display. any power. current and master switches lampoassa.fi. are on. A fuse has blown. Check the building’s master fuse and heat pump supply fuse.
  • Page 22: Alarms

    100% GEOTHERMAL HEAT MAINTENANCE MANUAL The system does A sudden drop in outdoor No action required. not produce enough temperature may temporari- heat. ly cause inadequate heating power in new buildings, because moisture contained in the structure takes up a lot of heat when it dries.
  • Page 23: Maintenance Procedures

    MAINTENANCE MANUAL 5.4. Maintenance procedures 5.4.2. Input and output statuses NOTE! Access to the maintenance menu is password-protected. Access to For the purpose and function of digital inputs and outputs, see equipment the maintenance menu is restricted to Lämpöässä installer training gradu- electrical diagrams.
  • Page 24: Running Information

    100% GEOTHERMAL HEAT MAINTENANCE MANUAL Digital Output (NO) Analog Output (Y) 1 Brine circuit 1 1 Heating circuit 1 regulation motor 4 Heating circuit 3 regulation motor/ Adjusment of domestic hot water 2 Heating circuit 2 regulation motor 5 Speed regulation of brine pump 3 Alarm signal 12 Immersion heater 4 3 Analog immersion heater control...
  • Page 25: Positioning Valve Control

    MAINTENANCE MANUAL The following settings are possible for all circuits: Setting Description Example Reverse control Reversing of position In the OFF position, if voltage (ON/OFF) valve adjustment is 0 V, the regulator is in its direction extreme right position. In the ON position, if voltage is 0 V, the regulator is in its extreme left position.
  • Page 26: Resistor Controlling Method

    100% GEOTHERMAL HEAT MAINTENANCE MANUAL 5.4.10. External alarm The heating time before heating element activation can be set under Additional heat settings in the Other set values screen. On this page, if in use, external alarm settings are defined. Status is eit- her info or fatal.
  • Page 27: Boiler Maximum Limits

    MAINTENANCE MANUAL running period of the day when time indicated in the rinse interval is full. Manual controlling settles the valve to the percentage indicated in the valve setting point. Lämpöässä unit Factroy setting Vmi 6-11 Vmi 14-17 Manual cooling for testing the function. This function is used to change the status of cooling function and temperature setting points manually.
  • Page 28: Warranty Conditions

    100% GEOTHERMAL HEAT WARRANTY CONDITIONS 6. WARRANTY CONDITIONS The manufacturer grants its products a two (2) year warranty from the caused by product installation to the place of use in contradiction with commissioning date specified in the product’s warranty certificate. During instructions for installation or use or otherwise incorrectly, or by product the warranty period, the manufacturer is responsible for that the product repair, modification or installation by some other party than the manufac-...
  • Page 29: Technical Specifications

    TECHNICAL SPECIFICATIONS 7. TECHNICAL SPECIFICATIONS Vmi 11 Vmi 14 LÄMPÖÄSSÄ Vmi 6 Vmi 9 Vmi 11 Vmi 14 Vmi 17 1x230 1x230 Width 1020 1020 1020 1020 1020 1020 1020 Depth Height 1830 1830 1830 1830 1830 1830 1830 Weight Heat pump type Brine-to-water Brine-to-water...
  • Page 30: Energy Label

    100% GEOTHERMAL HEAT TECHNICAL SPECIFICATIONS Vmi 11 Vmi 14 ELECTRICS: Vmi 6 Vmi 9 Vmi 11 Vmi 14 Vmi 17 1x230 1x230 400V 3N~ 400V 3N~ 400V 3N~ 230V 1N~ 400V 3N~ 230V 1N~ 400V 3N~ Power supply 50Hz 50Hz 50Hz 50Hz 50Hz...
  • Page 31 Vmi 6 8  8  8  2015 811/2013...
  • Page 32 Vmi 6 2015 811/2013...
  • Page 33 Seasonal space heating energy efficieny of package in warmer climate conditions Function Heating Average Warmer Colder Capacity control Fixed Design load Heating Average Pdesignh 7,75 Warmer Pdesignh 7,75 Colder Pdesignh 7,75 Seasonal efficiency Heating Average SCOP/A Warmer SCOP/W Colder SCOP/C www.lampoassa.fi...
  • Page 34 Maximum quantity od usable hot water Temperature operating range: minimal and maximal heaetsource temperature, -10/15 minimal start and maximal mean temperature domestic hot water. °C Contact detalis for obtaining more information Name manufacturer Suomen Lämpöpumpputekniikka Oy Address Unikontie 2, 62100 LAPUA, FINLAND www.lampoassa.fi...
  • Page 35 Vmi 9 10  10  10  2015 811/2013...
  • Page 36 Vmi 9 2015 811/2013...
  • Page 37 Seasonal space heating energy efficieny of package in warmer climate conditions Function Heating Average Warmer Colder Capacity control Fixed Design load Heating Average Pdesignh 9,82 Warmer Pdesignh 9,82 Colder Pdesignh 9,82 Seasonal efficiency Heating Average SCOP/A Warmer SCOP/W Colder SCOP/C www.lampoassa.fi...
  • Page 38 Maximum quantity od usable hot water Temperature operating range: minimal and maximal heaetsource temperature, -10/15 minimal start and maximal mean temperature domestic hot water. °C Contact detalis for obtaining more information Name manufacturer Suomen Lämpöpumpputekniikka Oy Address Unikontie 2, 62100 LAPUA, FINLAND www.lampoassa.fi...
  • Page 39 Vmi 11 11  11  11  2015 811/2013...
  • Page 40 Vmi 11 2015 811/2013...
  • Page 41 Seasonal space heating energy efficieny of package in warmer climate conditions Function Heating Average Warmer Colder Capacity control Fixed Design load Heating Average Pdesignh 11,5 Warmer Pdesignh 11,5 Colder Pdesignh 11,5 Seasonal efficiency Heating Average SCOP/A Warmer SCOP/W Colder SCOP/C www.lampoassa.fi...
  • Page 42 Maximum quantity od usable hot water Temperature operating range: minimal and maximal heaetsource temperature, -10/15 minimal start and maximal mean temperature domestic hot water. °C Contact detalis for obtaining more information Name manufacturer Suomen Lämpöpumpputekniikka Oy Address Unikontie 2, 62100 LAPUA, FINLAND www.lampoassa.fi...
  • Page 43 Vmi 11 1x230V 11  11  11  2015 811/2013...
  • Page 44 Vmi 11 1x230V 2015 811/2013...
  • Page 45 Seasonal space heating energy efficieny of package in warmer climate conditions Function Heating Average Warmer Colder Capacity control Fixed Design load Heating Average Pdesignh 11,2 Warmer Pdesignh 11,2 Colder Pdesignh 11,2 Seasonal efficiency Heating Average SCOP/A Warmer SCOP/W Colder SCOP/C www.lampoassa.fi...
  • Page 46 Maximum quantity od usable hot water Temperature operating range: minimal and maximal heaetsource temperature, -10/15 minimal start and maximal mean temperature domestic hot water. °C Contact detalis for obtaining more information Name manufacturer Suomen Lämpöpumpputekniikka Oy Address Unikontie 2, 62100 LAPUA, FINLAND www.lampoassa.fi...
  • Page 47 Vmi 14 14  14  14  2015 811/2013...
  • Page 48 Vmi 14 2015 811/2013...
  • Page 49 Seasonal space heating energy efficieny of package in warmer climate conditions Function Heating Average Warmer Colder Capacity control Fixed Design load Heating Average Pdesignh 14,5 Warmer Pdesignh 14,5 Colder Pdesignh 14,5 Seasonal efficiency Heating Average SCOP/A Warmer SCOP/W Colder SCOP/C www.lampoassa.fi...
  • Page 50 Maximum quantity od usable hot water Temperature operating range: minimal and maximal heaetsource temperature, -10/15 minimal start and maximal mean temperature domestic hot water. °C Contact detalis for obtaining more information Name manufacturer Suomen Lämpöpumpputekniikka Oy Address Unikontie 2, 62100 LAPUA, FINLAND www.lampoassa.fi...
  • Page 51 Vmi 14 1x230V 14  14  14  2015 811/2013...
  • Page 52 Vmi 14 1x230V 2015 811/2013...
  • Page 53 Seasonal space heating energy efficieny of package in warmer climate conditions Function Heating Average Warmer Colder Capacity control Fixed Design load Heating Average Pdesignh 13,7 Warmer Pdesignh 13,7 Colder Pdesignh 13,7 Seasonal efficiency Heating Average SCOP/A Warmer SCOP/W Colder SCOP/C www.lampoassa.fi...
  • Page 54 Maximum quantity od usable hot water Temperature operating range: minimal and maximal heaetsource temperature, -10/15 minimal start and maximal mean temperature domestic hot water. °C Contact detalis for obtaining more information Name manufacturer Suomen Lämpöpumpputekniikka Oy Address Unikontie 2, 62100 LAPUA, FINLAND www.lampoassa.fi...
  • Page 55 Vmi 17 17  17  17  2015 811/2013...
  • Page 56 Vmi 17 2015 811/2013...
  • Page 57 Seasonal space heating energy efficieny of package in warmer climate conditions Function Heating Average Warmer Colder Capacity control Fixed Design load Heating Average Pdesignh 16,7 Warmer Pdesignh 16,7 Colder Pdesignh 16,7 Seasonal efficiency Heating Average SCOP/A Warmer SCOP/W Colder SCOP/C www.lampoassa.fi...
  • Page 58 Maximum quantity od usable hot water Temperature operating range: minimal and maximal heaetsource temperature, -10/15 minimal start and maximal mean temperature domestic hot water. °C Contact detalis for obtaining more information Name manufacturer Suomen Lämpöpumpputekniikka Oy Address Unikontie 2, 62100 LAPUA, FINLAND www.lampoassa.fi...
  • Page 59 CURRENT MONITORING RELAY INSTALLATIONS AND CONNECTION These settings are initial and may require changing. Relays must always be adjusted in a case-specific manner. 1. Choose correct current range • Turn switch 2 to position ON (if master fuse size is less than 50 A) •...
  • Page 93 Lämpöässä is a trademark of Suomen Lämpöpumpputekniikka Oy. We reserve the right to make changes. Suomen Lämpöpumpputekniikka Oy Unikontie 2 62100 Lapua www.lampoassa.com...

This manual is also suitable for:

Vsi 6-14

Table of Contents