Page 2
187 40 TÄBY Sweden declare under own responsibility that the product: Dehumidifier DehuTech 2400 (type DA-2400 in Swedish market) from unit no 690502 which is detailed in this declaration complies to the following harmonised European standards and technical specifications: SS-EN 60335-1 issue 2...
General safety information • Anyone operating the DehuTech 2400 • The service panels should remain closed should have access to this manual, and except when servicing is carried out. should be aware of the safety information. • The dehumidifier can only be used for dehu- •...
Applications Method of operation Dehumidifier DehuTech 2400 is of the solid des- The dehumidifier operates with two air streams. iccant wheel type designed to dry air of atmos- A larger air stream to be dehumidified, and a pheric pressure. The dehumidifier can be used...
The centre hub of the rotor is equipped with ball long as it takes to cool off the heater element. bearings. The rotor shaft is made from stainless Never use the main powerswitch to stop the steel. machine, as it could overheat! Subject to change without notice DehuTech 2400...
Reactivation air into the dehumidifier Installation and service access The reactivation air duct into the dehumidifier Dehumidifier DehuTech 2400 is designed for should be as short as possible. The intake open- indoor installation, and must be installed in a ing of the duct should have a coarse wire net, to upright position, preferably bolted to the floor.
Compare the cal supply by turning the isolation switch to result with the performance chart on page 12. ON, and check that all three phases are live. Terminal L1, L2, L3 in the dehumidifier. Subject to change without notice DehuTech 2400...
The maintenance intervals for the dehumidifier Cleaning with water is no routine matter, please depend on the surrounding environment and contact DehuTech AB or local distributor prior installation site. Recommended maintenance to this procedure. intervals could therefore differ from one instal- Check the rotor bearing and the rotor surface lation to another.
• Never put other goods on top of the dehu- midifier. • Transport and lift the dehumidifier by fork- lift. Ensure that the forks go all the way to the back of the dehumidifier before lifting. Subject to change without notice DehuTech 2400...
No dry- or wet air volume Filter clogged Clean or replace filters Fan faulty Check fan, motor and impeller Phase fault Check main fuses and phase sequence Ducts blocked Check dampers and ducts Subject to change without notice DehuTech 2400...
Technical data Performance chart CAPACITY DIAGRAM =30°C =20°C �10°C (g/kg) EXAMPLE: Process air: x = 9,0 g/kg, t = +20°C giving Dry air: x = 3,3 g/kg, t = 20+20 = 40°C Subject to change without notice DehuTech 2400...
(3 x 400 V, 50 Hz) Current (A / phase) 37,5 A (connection fuse: 50 A / phase) Weight 190 kg Max noise level 75 dB(A) Note: Valid only for standard units, with standard air-flows. Subject to change without notice DehuTech 2400...
MB 22/9 T2M 2,2 kW Wet air fan MB 20/8 T2K 1,1 kW Heater Electrical Rotor PPS 2400 Process air filter Corrugated paper filter 715 x 494 x 45 mm Reactivation air filter Metal frame filter 300 x 300 x 25 mm...
Speed 2 850 2 750 Power 14,5 VA Voltage Frequency Amps 2,55 Power factor cos ϕ 0,84 0,84 Protection class Insulation class Specialties ROTOR Type PPS 2400 Rotor speed Continued on next page. Subject to change without notice DehuTech 2400...
Page 16