11.16.4 Control of the condenser fan

A temperature probe T2 is located on the discharge side of the condenser. The condenser fan is activated (ON) when
the T2 temperature is higher than FANon setting (standard 35°C / 96°F) and led
Condenser fan stops at T2 temperatures 5°C / 10°F lower than FANon setting (standard 30°C / 86°F).

11.16.5 Control of the drain solenoid valve (Not used)

Drain solenoid valve is activated (ON) for Ton seconds (standard 2 seconds) every Toff minutes (standard 1 minute).
Led
shows that condensate drain solenoid valve is ON.
The condensate drain test is always active using the button
11.16.6 Operating parameters – setup menu
The setup menu can be used to change the chiller's operating parameters.
Only qualified personnel must be allowed to access to the setup menu. The manufacturer is not
responsible for malfunctioning or failure due to modification to the operating parameters.
With chiller ON press button
Access to the menu is confirmed by led
Set
Keep
pressed and use arrows
Set
Press shortly
to skip to following parameter.
Press
to exit setup menu (if no button is pressed after 2 minutes the menu is exited automatically).
Display
Synchronous flashing
ON
led
+ led
Synchronous flashing
ON
led
+ led
Non-Synchronous flashing
ON
led
+ led
NOTE : parameter values are displayed on the 10 led display where 1st (left) led is the lowest limit and 10th (right) is
the highest limit.
BEKOBLIZZ® LC 12-355
Set
for at least 3 seconds to enter the setup menu.
ON
and
to change the value. Release the button
Description
FANon : condenser fan activation
(ON) temperature
Ton – drain time ON : not used
ToF - drain time OFF : not used
.
flashing (first parameter of menu).
Limits
31 ... 40 °C or
88 ... 104 °F
1 ... 10 sec
1 ... 20 min
Technical description
is ON.
Set
to confirm the value.
Standard
Resolution
setup
1 °C
or
2 °F
1 sec
1 min
35
or
96
2
1
31