8.2

Installation plan

Installation type A straight upstream of the application is recommended.
Installation type B is NOT recommended because of the low compressed air temperature there will be condensation
outside of the pipes and vessel and the air will be rewarmed.
Do not obstruct the ventilation grille (not even partially).
Prevent any recirculation of the outgoing cooling air.
Protect the chiller against draughts.
Note!
Contaminated intake air!
In the event that the intake air is strongly contaminated (ISO 8573.1 class 3.-3 or poorer quality), we
recommend the additional installation of a prefilter (e.g. CLEARPOINT F040), to avoid clogging of the
heat exchanger.
BEKOBLIZZ® LC 12-355
1
Air compressor
2
Aftercooler
3
Condensate separator
4
Prefilter
5
Bypass group
6
Chiller
7
Compressed-air tank
8
Final filter
9
Bekomat condensate drain
Installation