Delta Settings : The Delta T Setting is the delta, or difference between, the setpoint and
current temp for determining when a heat or cool call comes on. The "delta" is the number
of degrees away from setpoint.
H/C Delta
Sets the minimum separation between heating and cooling setpoints. Attempts to lower
the cooling below the heating setpoint by this amount will PUSH the heating setpoint down
to maintain this separation. Same for setting the heating setpoint above the cooling
setpoint, it will PUSH the cooling setpoint up to maintain this separation.
Heating Delta Stage 1 ON
Sets the delta from setpoint that stage 1 heating starts.
Heating Delta Stage 1 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 1 heating stops. Stage 1 turns off at setpoint
+ Delta Stage 1.
Heating Delta Stage 2 ON
Sets the delta from setpoint that stage 2 heating starts.
Heating Delta Stage 2 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 2 heating stops. Stage 2 turns off at setpoint
+ Delta Stage 2.
Heating Delta Stage 3 ON
Sets the delta from setpoint that stage 3 heating starts.
Heating Delta Stage 3 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 3 heating stops. Stage 3 turns off at setpoint
+ Delta Stage 3.
Cooling Delta Stage 1 ON
Sets the delta from setpoint that stage 1 cooling starts.
Cooling Delta Stage 1 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 1 Cooling stops. Stage 1 turns off at
setpoint - Delta Stage 1
Cooling Delta Stage 2 ON
Sets the delta from setpoint that stage 2 cooling starts.
Cooling Delta Stage 2 OFF Range: 0 to 8 degrees
Sets the delta from setpoint that stage 2 Cooling stops. Stage 2 turns off at
setpoint -Delta Stage 2.
Max Heat SP
Sets the maximum heating setpoint value. Will not ramp or accept setpoints higher that
this maximum.
Min Cool SP
Sets the minimum cooling setpoint value. Will not ramp or accept setpoints lower than this
minimum.
Minimum Run Time (MRT)
Sets the minimum run time before a heating/cooling cycle can turn off.
Sets heating/cooling cycle time. Prevents rapid cycling.
Minimum Off Time (MOT)
DCN: 140-01773-01
Range: 3 - 15 degrees.
Range: 1 to 8 degrees
Range: 1 to 8 degrees
Range: 1 to 8 degrees
Range: 1 to 8 degrees
Range: 1 to 8 degrees
Range: 40F to 109F (4C-43C) Default: 90F (32C)
Range: 44F to 113F (6C-45C) Default: 60F (15C)
Range: 1- 9 Minutes
Range: 5-9 Minutes
Default: 3F (1C)
Default: 1
Default: 0
Default: 2
Default: 0
Default: 3
Default: 0
Default: 1
Default: 0
Default: 2
Default: 0
Default: 3
Default: 5