Make Electrical Connections
Wiring
WARNING
HIGH VOLTAGE!
Goodman 6
Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage,
personal injury or death.
All wiring should be made in accordance with the National
Electrical Code (N.E.C). The local power company should be
consulted to determine the availability of sufficient power to
operate the unit. The voltage, frequency and phase at the power
supply should be checked to make sure it corresponds to the
unit’s rated voltage requirement.
Install a branch circuit fused disconnect near the unit, in
accordance with the N.E.C. or local codes. Wire sizes and over-
current protection should be determined from the unit nameplate
ampacity and in accordance with Branch Circuit Ampacity chart
or the N.E.C. Under no circumstances should wiring be sized
smaller than is recommended by either of these 2 sources.
Branch Circuit
Ampacity
Supply Wire
Length—ft (m)
15
20
25
30
35
40
45
50
200 (61)
6
4
4
4
3
3
2
2
150 (45.7)
8
6
6
4
4
4
3
3
100 (30.5)
10
8
8
6
6
6
4
4
50 (15.2)
14
12
10
10
8
8
6
6
Fuses smaller than that recommended on the wiring diagrams
could result in unnecessary fuse failure or service calls. The use
of protective devices of larger size than indicated could result in
extensive damage to the equipment. The manufacturer bears no
responsibility for damage caused to equipment as result of the
use of larger than is recommended size protective devices.
All units have undergone a run test prior to packaging for
shipment. This equipment has been started at minimum rated
voltage and checked for satisfactory operation. Do not attempt to
operate this unit if the voltage is not within the minimum and
maximum voltages shown on nameplate.
All exterior wiring must be within approved weatherproof conduit.
The unit must be permanently grounded in accordance with local
codes, or in absence of local codes, with N.E.C. ANSI/ NFPA No.
70-1984 or latest edition by using ground lug in the control box.
Fuses or HACR type circuit breakers may be used where codes
permit.
High Voltage Wiring
Single Phase—Connect the 2 leads to terminals L1 and L2 in the
electrical control section, using wire sizes specified in the wiring
table.
Page 6