Dual Gate Installations - Polaris 700 Installation Manual

Automatic gate operator
Hide thumbs Also See for 700:
Table of Contents

Advertisement

Dual Gate Installations

Step 1
Make sure both gates are in the fully open position.
Ensure power switch is in the ON position.
Step 2
Verify Block 2, DIP Switch #1 is in ON position. Press the cycle
button on the circuit board and the gates will begin to close.
Stop the gates using the cycle button when the desired limit
for the primary gate has been reached.
Step 3
Verify Block 2, DIP Switch #6 is in the OFF position. Press
and hold the "SET LIMIT" button until one audible beep is
heard to acquire the closed limit setting (fig. 28). The STATUS
light will turn on immediately upon pressing the SET LIMIT
button. The STATUS light will turn off and an audible beep
will verify the closed limit is now set.
Step 4
Press the cycle button on circuit board to return the gates to
the fully open position.
Step 5 (setting secondary gate)
Set Block 2, DIP switch #6 to the ON position. Again, press
the cycle button. The gates will begin to close. The primary
gate should stop at the closed limit position that was
programmed in the previous steps. The secondary gate will
continue to close until you press the cycle button on the
circuit board.
Step 6
Press and hold the "SET LIMIT" button until one audible
beep is heard to acquire the closed limit setting (fig. 28). The
STATUS light will turn on immediately upon pressing the SET
LIMIT button. The STATUS light will turn off and an audible
beep will verify the closed limit is now set.
Step 7
Press the cycle button on circuit board to open both gates.
Then once again press the button to close the gates and
verify the closed limits are set properly. If the gates did not
reach the desired closed limits, proceed to step 8.
PULL-TO-OPEN LIMIT SETTING
Figure 28
Step 8
CLEARING THE CLOSED LIMIT SETTINGS:
a) Return the gates to the fully open position.
b) Set Block 2, DIP switch #6 to the OFF position.
c) Press and hold the SET LIMIT button until two audible
beeps are heard.Two audible beeps will verify the closed
limit setting is now cleared.
d) Set Block 2, DIP switch #6 to the ON position.
e) Press and hold the SET LIMIT button until two audible
beeps are heard. Two audible beeps will verify the closed
limit setting is now cleared.
Repeat steps 1 – 7 to program the gates "closed limit
setting".