Page 2
Your HygroMatik steam humidifier will be carefully adapted to your particular application. Copyright HygroMatik GmbH; MiniSteam, July 2012 Information in this manual is subject to change or alteration without prior notice. Current version of this manual can be found at: www.hygromatik.co.uk Warning, Hazardous Voltage: All work to be performed by trained personnel only.
1. Introduction Dear Customer, Thank you for choosing a HygroMatik steam humidifier. HygroMatik steam humidifiers represent the latest in humidifica- tion technology. They will impress you with their safety, ease of use and econom- ical operation. In order to operate your HygroMatik steam humidifier safely, properly and efficiently, please read these operating instructions.
Use feed water with a conductivity between 125 and 1250 µS/ cm only Lower threshold Range of reduced conductivity Normal tap water Range of heightened conductivity Range of heigh conductivity Upper threshold Warning: HygroMatik steam humidifiers emit steam with a tem- perature of 100°...
2. Safety Notes 2.1 Overview These safety notes are required by law. They promote work- place safety and accident prevention. Warnings and Safety Symbols The safety symbols below identify sections containing warnings about hazards or potential dangers. Please familiarize yourself with these symbols.
safely leads the steam. HygroMatik steam humidifiers are IP20-protected. Make sure that the unit is protected from drips in its installed location. Installing a humidifier in a room without water discharge requires safety devices to protect against water leakages. Accident Prevention Regulations Comply with the Accident Prevention Regulation Electrical Sys- tems and Equipment to prevent injury to yourself and others.
3.3 Packing Note: Notice the symbols affixed to the packing box. 3.4 Interim Storage Store the unit in a dry place and protect from frost. 3.5 Check for Complete and Correct Delivery of Goods Upon receipt of the unit, confirm that: ...
4. Operation and Installation 4.1 Mode of Operation The HygroMatik steam humidifier utilizes the conductivity nor- mally present in tap water for steam production. Electrodes inside an enclosed steam cylinder are immersed directly into the tap water. They are connected to the alternating current. The conductivity of the water generates an electric current between the electrodes.
Page 12
Please also see Section „Exploded View“. Location Designation steam nozzle vent pipe max. water level sensor electrode water drain, discharge top part of steam cylinder o-ring cylinder flange cylinder flange and o-ring lower part of cylinder solenoid valve water inlet blow-down pump o-ring cylinder base...
Page 13
The concentration of dissolved salts increases over time, which can lead to a rise in the conductivity of the water. If this contin- ues, conductivity may increase until a short circuit occurs. This could damage the unit, but in any case would significantly reduce the life span of the electrodes.
Page 14
The steam cylinder consists of a top (16) and lower (19) part joined with a cylinder flange. The seal between the cylinder and cylinder base (37), as well as between the top and lower part of the cylinder, is maintained using an o-ring (35). Warning: ...
5. Installation Warning: Installation of this unit to be attempted only by quali- fied personnel. We accept no liability for damage due to faulty installation. Obey all safety notes and warnings present on the unit. During installation the unit must be disconnected from its power supply.
Wall Mounting Note: The steam humidifier must be installed vertically in order to function properly. Note: The steam humidifier should be positioned such that draught effects are avoided. The minimum height is 0.15 m above floor level but we propose a height of 2m in order to avoid scalding.
6. Water Installation Warning: When installing the water installation, note the follow- ing: Have all work performed by a professional. Disconnect power supply before installation. Obey local public utility regulations Verify that necessary safety measures have been taken –...
Note: Please contact HygroMatik if you wish to operate the unit with softened water. If using a water softening system, we recommend diluting the softened water with normal tap water to produce an overall hard- ness between 4-8°dH. This value can be set lower if the water does not foam.
» Use a cap nut (internal thread ¾“) with inner seal for a customer-provided water installation. 6.3 Water discharge min.: 250mm max.: 1000mm Warning: During blow down hot water with a temperature of about 95°C is being drained. If touched this can cause burns to the skin.
There is a 3mm-wide crack between the pump drain hose jacket and the inner surface of the housing drain connection. If water collects in the base plate, it will flow through this crack into the drainage system. 6.4 Water Installation Check Go down the following water installation checklist: ...
7. Electrical Connection Danger, Hazardous Voltage: All work related to electrical instal- lation to be performed by authorized personnel only (electricians or professionals with equivalent training). The customer is responsible for checking qualifications. Danger, Hazardous Voltage: Do not plug the steam humidifier into the power grid until after all installation work has been com- pleted.
Page 24
Type Standard Main Power Supply HY05 - HY45 1 x 400V/3Phase/N HY60 - HY116 2 x 400V/3Phase/N C01, C02 1 x 230/1Phase/N C06 - C58 1 x 400V/3Phase/N MS5, MS10 1 x 400V/3Phase/N 1 x 230/1Phase/N DBE 2 1 x 230V/1Phase DBE 6-45 1 x 400V/3Phase/N Other voltages are available on request.
MiniSteam: Type Power Usage Circuit Protection MS5, 230V/1/N 15,7 A 1 x 16 A MS5, 400V/3/N 5,4 A 3 x 6 A MS10, 400V/3/N 10,8 A 3 x 16 A DBE: Type Power Usage Circuit Protection DBE1 3,3 A 1 x 6 A...
After this check the unit can be switched on. Warning: The unit must be closed and locked. This guarantees that the cover is grounded. (only humidifier type HyLine and MiniSteam) Note: For initial operation, control, service, malfunctions, and circuit diagrams, consult the operation instructions for the Hygro- Matik-controls.
8. Maintenance The HygroMatik steam humidifier is easy to maintain. However, inadequate or improper maintenance can lead to operational malfunctions. Perform regular maintenance to give your unit a long life span. Warning: When performing maintenance work, please note: During operation and also for a while after switching off the unit the steam cylinder is hot.
8.1 Maintenance Work Mineral deposits precipitate and crystallize very differently in dif- ferent types of water, even when two types have the same con- ductivity and hardness levels (the various constituents in the water interact differently). Instructions on maintenance and cleaning intervals, or on elec- trode service life, are based entirely on empirical data Cycle Maintenance Work...
Page 29
» The basic PCB (C) is now accessable. Danger, Hazardous Voltage: Make sure the unit is switched off before installing or removing the display plate. Page 29...
8.3 Removing and Cleaning the Steam Cylinder Warning: Please follow the detailed instructions in these operat- ing instructions! The unit is only to be serviced by qualified, authorized personnel. Note the warnings and safety notes in the operating instructions. Failure to observe warnings and safety notes may result in injury, serious injury or death, and/or dam- age to the unit.
Page 31
» then: Cleaning Warning: Check the inside of the top part of steam cylinder for crust build-up and possible salt bridges (black grooves between the electrode leads). If present, wash away completely . Note: If electrical arcs have burned deep grooves in the mate- rial, the top part of the cylinder must be replaced.
Page 32
Reassembly » Connect plug (10) to level sensor. » Connect plugs (4) to electrodes. » Warning: The plug must be pressed down onto the electrode as far as it will go. Note: Connect plugs to the correct electrodes. Note the color of the knurled nut.
8.4.1 Original Electrode Lengths Original lengths of HygroMatik large area stainless-steel elec- trodes are: HyLine: Type HY05-HY08 HY13-HY60 HY90-HY116 Length [mm] CompactLine: Type C6 C10 C17-45 C58 Length [mm] 125 155 MiniSteam: Type MS10 Length [mm] Page 33...
8.4.2 Uneven Electrode Lengths In most case, the longer electrode(s) will not be supplied with electricity for a time. Therefore they will not wear. The cause of the problem, such as a tripped circuit breaker, can be repaired. However, since the shorter electrode(s) have a greater specific load, the electrodes continue to wear unevenly.
Page 35
» Remove cylinder, as described in Chapter 8.3 "Remov- ing and Cleaning Steam Cylinder." » Loosen knurled nuts (5) and remove electrodes (48). » Install new electrodes and hand tighten the nuts. » Use solvent-free, HygroMatik-quality o-rings (for flange, cylinder base and steam hose adapter). »...
8.6 Cleaning the Blow- Down Pump » Remove cylinder, as described in Section: "Removing and Cleaning the Steam Cylinder” » Detach e-cable from the pump. » Detach adapter (30) from the pump. » Loosen screws (44) and remove the pump from the base.
» Place solenoid valve with seal in the borehole of the unit housing. » Attach solenoid valve tightly with screws (28). » Screw on water installation hose. » Connect e-cable to the solenoid valve. » Attach connecting hose (21) to the base. »...
9. Commissioning Warning: This unit is only to be started by qualified personnel. Switching off steam humidifier Warning: Before starting up the unit, make sure you know how to switch it off. » Switch off unit by setting control switch to “0” »...
11. Spare Parts MS5 MS10 Article no. Description E-2124010 Keys for safety, set=2pc. Safety lock incl. 2 keys E-2124012 Steam generation Steam cylinder CY4 transp. compl. with electrodes and Hand nuts ** B-3216067 Steam cylinder CY8 transp. compl. with electrodes and Hand nuts ** B-3204031 Top part of steam cylinder CY4 empty E-3216043...
12. Fax Form - Order for spare parts Fax Form Please copy, fill in and fax to HygroMatik . +49(0)4193/895-31 Lise-Meitner-Str. 3 Fax.No 24558 Henstedt-Ulzburg Tel. +4904193/895-0 Order of spare parts unit type *______________ serial no.* ___________________ commission: ______________ order no.: __________________ quantity article article no.
13. Technical Data Technical Data Steam Humidifiers MiniSteam Type MS10 Steam Output [kg/h] Electrical Supply 230V/1/N/50-60Hz 400V/3/N/50-60Hz Electrical Power [kW] Current [A] 15,7 10,8 Fuse [A] 1 x 16 * 3 x 6 * 3x 16 * Control Type Basic, Comfort...