Error Codes Table - Panasonic CS-E7LKEW Service Manual

Hide thumbs Also See for CS-E7LKEW:
Table of Contents

Advertisement

16.3.

Error Codes Table

Diagnosis
Abnormality /
display
Protection control
H00
No memory of failure
H11
Indoor/outdoor
abnormal
communication
H12
Indoor unit capacity
unmatched
H14
Indoor intake air
temperature sensor
abnormality
H15
Compressor
temperature sensor
abnormality
H16
Outdoor current
transformer (CT)
abnormality
H19
Indoor fan motor
merchanism lock
H23
Indoor heat exchanger
temperature sensor
abnormality
H25
Indoor E-Ion
abnormality
H27
Outdoor air temperature
sensor abnormality
H28
Outdoor heat exchanger
temperature sensor 1
abnormality
H30
Outdoor discharge pipe
temperature sensor
abnormality
H32
Outdoor heat exchanger
temperature sensor 2
abnormality
H33
Indoor / outdoor
misconnection
abnormality
H34
Outdoor heat sink
temperature sensor
abnormality
H36
Outdoor gas pipe
temperature sensor
abnormality
H37
Outdoor liquid pipe
temperature sensor
abnormality
H38
Indoor/Outdoor
mismatch (brand code)
Abnormality
Protection
Judgement
operation
Normal operation
After operation for
Indoor fan only
1 minute
operation can
start by entering
into force cooling
operation
90s after power
supply
Continuous for 5s
Continuous for 5s
Continuous
happen for 7 times
Continuous for 5s
Port is ON for 10s
during E-Ion off
Continuous for 5s
Continuous for 5s
Continuous for 5s
Continuous for 5s
Continuous for 2s
Continuous for 5s Heating protection
operation only
Continuous for 5s Cooling protection
operation only
Problem
Indoor/outdoor
communication not establish
Total indoor capability more
than maximum limit or less
than minimum limit, or
number of indoor unit less
than two.
Indoor intake air temperature
sensor open or short circuit
Compressor temperature
sensor open or short circuit
Current transformer faulty or
compressor faulty
Indoor fan motor lock or
feedback abnormal
Indoor heat exchanger
temperature sensor open or
short circuit
Outdoor air temperature
sensor open or short circuit
Outdoor heat exchanger
temperature sensor 1 open
or short circuit
Outdoor discharge pipe
temperature sensor open or
short circuit
Outdoor heat exchanger
temperature sensor 2 open
or short circuit
Indoor and outdoor rated
voltage different
Outdoor heat sink
temperature sensor open or
short circuit
Outdoor gas pipe
temperature sensor open or
short circuit
Outdoor liquid pipe
temperature sensor open or
short circuit
Brand code not match
92
Check location
• Indoor/outdoor wire terminal
• Indoor/outdoor PCB
• Indoor/outdoor connection wire
• Indoor/outdoor connection wire
• Indoor/outdoor PCB
• Specification and combination
table in catalogue
• Indoor intake air temperature
sensor lead wire and connector
• Compressor temperature sensor
lead wire and connector
• Outdoor PCB faulty or
compressor faulty
• Fan motor lead wire and
connector
• Fan motor lock or block
• Indoor heat exchanger
temperature sensor lead wire and
connector
• E-Ion PCB
• Outdoor air temperature sensor
lead wire and connector
• Outdoor heat exchanger
temperature sensor 1 lead wire
and connector
• Outdoor discharge pipe
temperature sensor lead wire and
connector
• Outdoor heat exchanger
temperature sensor 2 lead wire
and connector
• Indoor and outdoor units check
• Outdoor heat sink sensor
• Outdoor gas pipe temperature
sensor lead wire and connector
• Outdoor liquid pipe temperature
sensor lead wire and connector
• Check indoor unit and outdoor
unit.