[030] Zone Loop Response
Option
Description
[1]
ON: Zone 33 is Fast Loop Response: Zone 33 has a fast loop response (36 ms).
OFF: Zone 33 is Normal Loop Response: Zone 33 has a normal loop response (400 ms).
[2]
ON: Zone 34 is Fast Loop Response: Zone 34 has fast loop response (36 ms).
OFF: Zone 34 is Normal Loop Response: Zone 34 has normal loop response (400 ms).
[3]-[8]
For Future Use

[101]-[134] Zone Attributes

The following options can be enabled or disabled for each zone. Pressing [9] in one of these sections brings the installer to the upper bank (attributes 9 to 16). From
the upper bank, press [9] to return to the lower bank (attributes 1 to 8).
i
These attributes override default settings. Do NOT change fire zone attributes from their default settings.
Option
[1]
Bell Options
i
If a zone is set for silent alarm, and 2-way Audio (attribute [9]) is enabled, the audio session will only be Listen-in. This means the central station
operator can not speak back through the system to the end user. (This applies to the PC5950 audio verification module only).
[2]
Bell Type
[3]
Chime
[4]
Bypass
[5]
Force Arming
[6]
Swinger
Shutdown
i
If a zone is in Swinger Shutdown, and this attribute is disabled, then re-enabled, the zone will no longer be in Swinger Shutdown.
[7]
Transmission
Delay
[8]
Cross Zone
[9]
2-way Audio
[10]-[13]
For Future Use
Options [14] to [16] are used for zones 33 and 34 exclusively. If more than 1 option is enabled for options 14, 15, and 16 the lowest attribute number will take pre-
cedence. If Options 14 and 15 are both enabled the zone follows the NC loop configuration.
[14]
Normally
Closed
Loops
[15]
Single End of
Line (SEOL)
Resistors
[16]
Double End of
Line (DEOL)
Resistors
ON: An alarm activates the bell output.
OFF: Silent alarm.
ON: The bell output is steady when the zone is in alarm.
OFF: The bell output pulses when the zone is in alarm.
ON: The keypad chimes when the zone is violated and when the zone is secured.
OFF: The zone does not chime the keypad.
ON: The zone may be manually bypassed.
OFF: The zone can not be bypassed.
ON: The system can be armed with the zone violated. The zone is temporarily bypassed and, when secured, is monitored by
the system.
OFF: The system cannot be armed if the zone is open.
ON: When the zone goes into alarm for the number of times programmed in the Swinger Shutdown Counter (see section
[377]), it shuts down with no further transmissions sent to the monitoring station. The bell follows Swinger Shutdown if pro-
grammed.
OFF: Swinger Shutdown is disabled. All alarms are transmitted and do not follow the Swinger Shutdown Counter.
ON: Reporting of zone alarms are delayed for the programmed time in section [377] after the zone goes into alarm. If a valid
access code is entered within this time, no alarm signal is communicated.
OFF: When an alarm occurs, the reporting code is transmitted immediately.
ON: The zone is enabled for cross zoning.
OFF: The zone is not enabled for cross zoning.
Applies to 2-way Audio Verification Module (PC5950)
ON: The zone initiates a 2-way audio verification session with the central station.
OFF: The zone does not initiate a 2-way audio session.
ON: The zone follows the Normally Closed (NC) loop configuration.
OFF: The zone does NOT follow NC loop configuration.
ON: The zone follows the SEOL zone configuration.
OFF: The zone does NOT follow SEOL zone configuration.
ON: The zone follows the DEOL zone configuration.
OFF: The zone does NOT follow DEOL zone configuration.
Description
5-31
5.3 Programming Descriptions