Pressure Relief Valve; Part 2; Electrical Connection - Heat Transfer Munchkin VWH User Manual

High efficiency hot water supply boiler
Table of Contents

Advertisement

If the Munchkin is set up for liquefied petroleum (LP) gas, some geographic areas follow the Uniform
Mechanical Code, section 304.6, "Liquefied petroleum gas burning appliances shall not be installed in
a pit, basement or similar location where heavier-than-air gas might collect. Appliances so fueled, shall
not be installed in a below grade under-floor space or basement unless such location is provided with
an approved means for removal of unburned gas."
Condensation removal: This is a condensing, high efficiency appliance, therefore
condensation removal must be addressed to avoid damage to surrounding area or
appliance. See Part (4) for Condensate Requirements.
D. PRESSURE RELIEF VALVE
A pressure relief valve is installed into the right front side of the manifold. It is required that it meets
the requirements of ANSI/ASME Boiler and Pressure Vessel Code, Section IV or CSA B51: Boiler
Pressure Vessel and Piping Code as applicable for heating boilers. A ¾" pipe connected to the pressure
relief valve must be directed to a floor drain or suitable location within 6" of a drain or floor. To protect
the valve from freezing, do not plug or cap the pressure relief valve.
Serious explosion causing property damage and/or loss of life could result. Under no
circumstances should the relief valve be eliminated, capped or plugged.
PART 2. ELECTRICAL
A. ELECTRICAL CONNECTION
The electrical connection for the Munchkin is on the left hand side of the unit. There is a ½" knockout
location for an electrical connection for both the incoming power and the circulator connection. All
electrical wiring must be performed by a qualified licensed electrician in accordance with National
Electrical Code ANSI/NEPA to and/or the Canadian Electrical Code, Part 1 CSA C22.1, or to the
applicable codes and standards. For your convenience, we have labeled all the wires that need to be
connected to operate the Munchkin.
The electrical requirements are for standard 120 volts, 60 Hz 15 Amp service. This unit is wired with
#18 awg and fused for no more than 15 Amps.
IT IS EXTREMELY IMPORTANT THAT THIS UNIT BE PROPERLY GROUNDED!
IT IS VERY IMPORTANT THAT THE BUILDING GROUND IS INSPECTED BY A
QUALIFIED ELECTRICIAN PRIOR TO MAKING THIS CONNECTION!
There are two ground points in the electrical compartment that must be connected to the building
ground system. Connect the building ground to the green ground screw and the green ground wire
inside electrical box provided.
The Incoming power supply is connected to the Black (Hot) and the White (Neutral).The Munchkin
Control board is polarity sensitive. If the polarity is reversed, the Munchkin control will not sense a
flame and lock out the system.
n
NOTICE
n
DANGER
n
DANGER
n
DANGER
GENERAL INFORMATION
9