Zoning With Circulators - Munchkin Gas-fired Hot Water Boiler Manual

Hide thumbs Also See for Gas-fired Hot Water Boiler:
Table of Contents

Advertisement

GAS-FIRED BOILER
Munchkin VISION 1 system

(zoning with circulators)

Space heating mode
make-up water
anti-scald mixing valve
cold
water
Super Stor
indirect DHW tank
NOTES:
1.
This drawing is meant to show system piping concept only.
Installer is responsible for all equipment & detailing required by local codes.
2.
All closely spaced tees shall be within 4 pipe diameter center to center spacing.
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream
3.
of all closely spaced tees.
The minimum pipe size for connecting a Super Stor water heater is 1 inch.
4.
5.
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.
All pumps are shown with isolation flanges and integral flow check valves.
6.
The alternative is standard flanges with full port ball valves and a separate flow check valve.
7.
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.
8.
Install a minimum of 12 diameters of straight pipe upstream of all circulators.
9.
A purging valve may be used in lieu of the ball valve / hose bib combination shown.
31
purge
closely spaced tees
DHW
temperature
sensor
OFF
P2
thermal trap
(w/ drain plug)
make-up water
high limit safety
P1
T/P
purge
Munchkin boiler
Boiler Manual
Drawing 4A
zone
circulators
outdoor
temperature
sensor