LG AP-Z Series Service Manual page 33

Floor standing type air conditioner
Hide thumbs Also See for AP-Z Series:
Table of Contents

Advertisement

2) Balance refrigerant of the 3-way valve
(Gas leakage)
• Procedure
(1) Confirm that both the liquid side and gas side
valves are set to the back seat.
(2) Connect the charge set to the 3-way valve's
port.
– Leave the valve on the charge set closed.
– Connect the charge hose to the service port.
Indoor unit
Lo
OPEN
Liquid side
3-Way
valve
Gas side
3-Way
valve
CLOSE
(3) Open the valve (Lo side) on the charge set
and discharge the refrigerant until the gauge
indicates 0 kg/cm
– If there is no air in the refrigerant cycle (the
pressure when the air conditioner is not run-
ning is higher than 1 kg/cm
refrigerant until the gauge indicates 0.5 to 1
kg/cm
sary to apply a evacuatin.
– Discharge the refrigerant gradually; if it is dis-
charged too suddenly, the refrigeration oil will
also be discharged.
Outdoor unit
Open
Open
2
G.
2
G. if this is the case, it will not be neces-
Service Manual 33
3-way valve
2
G), discharge the