Fujitsu ASU09RL2 Service Instructions Manual page 36

Split type room air conditioner wall mounted type inverter
Table of Contents

Advertisement

Trouble shooting 11
OUTDOOR UNIT Error Method:
Outdoor unit Heat Ex. liquid temp.
sensor error
Detective Actuators:
Outdoor unit Main PCB
Heat exchanger temperature thermistor
Forecast of Cause :
1. Connector connection failure
Check Point 1 : Check connection of Connector
Check if connector is removed.
Check erroneous connection.
Check if thermistor cable is open.
>>Upon correcting the removed connector or mis-wiring, reset the power.
OK
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Check Point 2 :
Thermistor Characteristics (Approx. value)
Temperature
Resistance Value (k )
Temperature
Resistance Value (k )
If Thermistor is either open or shorted, replace it and reset the power.
OK
OK
Check Point 3 :
Check Point 3 : Check voltage of Main PCB (DC5.0V)
Make sure circuit diagram of outdoor unit and check terminal voltage at Thermistor (DC5.0V)
THERMISTOR
(PIPE)
BLACK
BLACK
BLACK
BLACK
THERMISTOR
(DISCHARGE)
THERMISTOR
(OUTDOOR)
BLACK
BLACK
If the voltage does not appear, replace Main PCB.
Indicate or Display:
Refer to error code table.
Detective details:
When Heat exchanger temperature thermistor open or
short-circuit is detected at power ON or while running the compressor.
2.Thermistor failure
-10°C
-5°C
0°C
(14°F)
(23°F)
(32°F)
(41°F)
27.21
20.80
16.05
12.47
40°C
50°C
60°C
70°C
(104°F)
(122°F)
(140°F)
(158°F)
2.606
1.759
1.213
0.8531
1
1
2
2
CN71
3
3
4
4
1
1
CN70
2
2
3
3
3. Main PCB failure
5°C
10°C
20°C
30°C
(50°F)
(68°F)
(86°F)
3.947
9.775
6.129
80°C
(176°F)
0.6115