LG AS-W096ERH0 Svc Manual page 61

Universal air conditioner
Hide thumbs Also See for AS-W096ERH0:
Table of Contents

Advertisement

Error code
Description
Over current Error
7
(CT2)
Check flow
Supplied voltage to
Outdoor pcb is about
AC 220/240V ?
No
Check power source
YES
Current sensing circuit is right ?
Check current sensing circuit.
- check CT is damaged in outdoor pcb
(output wire is disconnected to pin or not)
- BD01N is inserted in right position
(refer marking on pcb and component)
- Spec of R01N (1kΩ), R02N (1.65kΩ) is correct
- Direction of diode (D01N, D02N) is right
Copyright ©2007 LG Electronics. Inc. All right reserved.
Only for training and service purposes
• Supplied power is not normal
• Indoor/outdoor fan is locked
• Too much refrigerant
• Defect in current sensing circuit in outdoor pcb assembly
YES
Does indoor / outdoor fan work
normally ?
No
Check indoor / outdoor fan and
adjust.
No
Cause of error
YES
- 61 -
Troubleshooting Guide
Refrigerant pressure is right ?
No
Check refrigerant pressure
and adjust.
LGE Internal Use Only