Majestic 24VL Installation And Operating Instructions Manual

Majestic 24VL Installation And Operating Instructions Manual

Unvented gas log heater natural gas or propane/lpg control type: millivolt

Advertisement

Unvented Gas Log
Heater
Installation and Operating
Instructions
MODELS: 18VL, 24VL and 30VL
Natural Gas or Propane/LPG
Control Type: Millivolt
The design of this appliance complies with Standard Z21.11.2 of the American National Standards Institute
and is so certified by the International Approval Service.
In accordance with Standard Z21.11.2, this appliance may be operated as an unvented heater when installed
in a solid-fuel burning fireplace with the flue damper closed or an ANSI approved ventless firebox enclosure.
Follow the applicable instructions contained in this manual. (State or Local Codes may only allow operation of
this appliance in a vented configuration. Check your state or local codes.)
This appliance may be installed
in an aftermarket, permanently
located, manufactured (mobile)
home, where not prohibited by
local codes.
This appliance is only for use
with the type of gas indicated on
the rating plate. This appliance is
not convertible for use with other
gases.
This is an unvented gas-fired
heater. It uses air (oxygen)
from the room in which it is
installed. Provisions for adequate
combustion and ventilation air
must be provided.
Refer to page 7.
If the information in this manual is not followed exactly,
a fire or explosion may result causing property damage,
personal injury or loss of life.
Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any other
appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any
• Immediately call your gas supplier from a neighbor's
• If you cannot reach your gas supplier, call the fire
Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
READ AND SAVE THESE INSTRUCTIONS
530501
18 24 30VL
cover
WARNINGS
phone in your building.
phone. Follow the gas supplier's instructions.
department.
53D0501 7/09 Rev. 7

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 24VL and is the answer not in the manual?

Questions and answers

Summary of Contents for Majestic 24VL

  • Page 1 Unvented Gas Log Heater Installation and Operating Instructions MODELS: 18VL, 24VL and 30VL Natural Gas or Propane/LPG Control Type: Millivolt The design of this appliance complies with Standard Z21.11.2 of the American National Standards Institute and is so certified by the International Approval Service.
  • Page 2: Table Of Contents

    Do not use this appliance if any part has been under water. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control, which has been under water. 18VL, 24VL, 30VL Certified To ANSI Z21.11.2a-2008 Unvented Heaters &...
  • Page 3: 18/24/30Vl Unvented Gas Logs

    IMPORTANT SAFETY INFORMATION 18/24/30VL Unvented Gas Logs INSTALLER OWNER Please leave these instructions with the appliance. Please retain these instructions for future reference. IMPORTANT Read these instructions carefully before installing or trying to operate this vent-free gas heater. This appliance, as any gas-fired appliance, can produce poisonous carbon monoxide along with other combustion products.
  • Page 4 IMPORTANT SAFETY INFORMATION 18/24/30VL Unvented Gas Logs 18VL, 24VL and 30VL gas log appliances are design certified as unvented room appliances for installation in Never connect unit to private (non- an ANSI approved ventless firebox enclosure. utility) gas wells. This gas is commonly Notice: If installed in a VF32-R, VF36-R, VF42-R, EVB36, known as wellhead gas.
  • Page 5: Product Features And Specifications

    PRODUCT FEATURES and SPECIFICATIONS 18/24/30VL Unvented Gas Logs NATURAL GAS NOTE: An external regulator is required to reduce supply pressure to a maximum of 10 " W.C. on natural gas systems operating at higher pressure. Manual Pressure Milli-Volt and T-stat Pressure Regulator Pressure Setting: 3.0"...
  • Page 6: Fireplace And Hearth Dimensions

    FIREPLACE and HEARTH DIMENSIONS 18/24/30VL Unvented Gas Logs This appliance is for installation only in a solid-fuel burning masonry or UL127 factory- built fireplace, vent free appliance, or in listed ventless firebox enclosure. It has been design certified for these installations. Exception: DO NOT install this appliance in a factory-built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs.
  • Page 7: Clearances

    CLEARANCES 18/24/30VL Unvented Gas Logs The minimum clearance to any combustible item in front of this appliance should be no less than 36 inches from the face of the fireplace in which this appliance is installed. Any combustible mantel present on the fireplace facing of any fireplace in which this appliance is installed must not extend more than 12 inches from the face of the fireplace.
  • Page 8: How This Appliance Operates

    HOW THIS APPLIANCE OPERATES 18/24/30VL Unvented Gas Logs This appliance is equipped with a pilot burner, two main Never use this appliance to dry clothes, cook on burners, and an ignition tube, which connects the two or for any purpose other than providing heat into main burners.
  • Page 9: Gas Piping And Gas Pressure Requirements

    GAS PIPING and GAS PRESSURE REQUIREMENTS 18/24/30VL Unvented Gas Logs All gas piping must be installed to comply with local codes or, in the absence of local codes, with the National Fuel Gas Code ANSI Z223.1/NFPA 54. Only flexible hoses listed by a certified agency may be used.
  • Page 10: Combustion And Ventilation Air Requirements

    COMBUSTION and VENTILATION AIR REQUIREMENTS 18/24/30VL Unvented Gas Logs As do all gas-fired appliances, this appliance requires If the area in which this appliance may be fresh air (oxygen) for proper combustion and ventilation. operated is smaller than that defined as an In some cases, but not all, normal air infiltration into a unconfined space or if the building is of unusually building will supply a sufficient amount of fresh air for...
  • Page 11 COMBUSTION and VENTILATION AIR REQUIREMENTS 18/24/30VL Unvented Gas Logs This appliance shall not be installed in a confined The ODS (Oxygen Depletion Sensor) Pilot light space or unusually tight construction unless safety system is not a substitute for proper provisions are provided for adequate combustion installation and use of this appliance.
  • Page 12: Electrical Wiring (Milli-Volt)

    ELECTRICAL WIRING (MILLI-VOLT) 18/24/30VL Unvented Gas Logs The milli-volt valve is a self-powered combination gas control THAT DOES NOT REQUIRE 110 VAC TO OPER- ATE. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
  • Page 13: Connecting Remote Receiver

    ELECTRICAL WIRING (MILLI-VOLT) 18/24/30VL Unvented Gas Logs CONNECTING REMOTE RECEIVER THESE INSTRUCTIONS SUPERSEDE THE SECTION ENTITLED "HEARTH MOUNT" IN THE MILLIVOLT HAND HELD REMOTE INSTRUCTIONS SUPPLIED WITH THE REMOTE. 1. Plug wire into the back of the remote receiver. 2. Connect the other end of the wire harness to the wire harness attached to the unit located on the left side.
  • Page 14: Installation And Adjustment

    INSTALLATION and ADJUSTMENT 18/24/30VL Unvented Gas Logs Use these instructions as a guide while installing and This appliance is for installation only in a solid- adjusting this gas log appliance. The installation must fuel burning masonry fireplace or a UL 127 conform with local codes or, in the absence of local factory-built fireplace or a listed ventless firebox codes, with the National Fuel Gas Code ANSI Z223.1/...
  • Page 15: Pilot Flame

    INSTALLATION and ADJUSTMENT 18/24/30VL Unvented Gas Logs 6. Set the appliance base assembly in the fireplace and Do not use candles, matches or other ignition connect the gas supply line to the main regulator of sources when checking for gas leaks. Fuel gases the appliance.
  • Page 16 INSTALLATION and ADJUSTMENT 18/24/30VL Unvented Gas Logs 9. After the pilot flame is established, turn the appliance's Incorrect placement of the logs on the base control knob counterclockwise to low then press the can cause the production of carbon monoxide control knob inward slightly and continue turning gas and soot.
  • Page 17: Log Placement

    LOG PLACEMENT 18/24/30VL Unvented Gas Logs SPLENDOR GLOW FIBER LOG PLACEMENT Refer to Figure 12 1. Position the metal log support assembly on the base by aligning the notches of the log support assembly with the corresponding four log stops and two rear tabs of the base. 2.
  • Page 18: Refractory Log Placement

    LOG PLACEMENT 18/24/30VL Unvented Gas Logs REFRACTORY LOG PLACEMENT 1. Set the back log in position with the locating pins behind the log stops as shown in Figure 13. 2. Set the middle log in position with the locating pins behind the log stops. The middle log can be identified by the burned area in its center.
  • Page 19: Lighting Instructions

    LIGHTING INSTRUCTIONS 18/24/30VL Unvented Gas Logs WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns. WARNING: Do not use a blower insert, heat exchanger insert or other accessory not approved for use with this appliance. CAUTION: This appliance is hot while in operation.
  • Page 20: For Your Safety Read Before Lighting

    OPERATING INSTRUCTIONS 18/24/30VL Unvented Gas Logs FOR YOUR SAFETY READ BEFORE LIGHTING If you do not follow these instruction exactly, a fire or explosion may result causing property damage, personal injury or loss of life. A. This appliance is equipped with a piezo ignition device which lights the pilot. If piezo is not working properly see Match Lighting Instructions.
  • Page 21: Manual Control Lighting Instructions

    OPERATING INSTRUCTIONS 18/24/30VL Unvented Gas Logs MANUAL CONTROL LIGHTING INSTRUCTIONS 1. STOP! Read the safety information. 2. Make sure the manual shutoff valve is fully open. 3. This heater is equipped with an ignition device (piezo) which automatically lights the pilot. 4.
  • Page 22: Milli-Volt Control Lighting Instructions

    OPERATING INSTRUCTIONS 18/24/30VL Unvented Gas Logs MILLI-VOLT CONTROL LIGHTING INSTRUCTIONS 1. STOP! Read the safety information label. 2. Make sure the manual shutoff valve is fully open. 3. This gas log set is equipped with an ignition device (piezo) which automatically lights the pilot. If piezo ignitor does not light the pilot, refer to Match Lighting Instructions, page 29.
  • Page 23: Thermostat Control Lighting Instructions

    OPERATING INSTRUCTIONS 18/24/30VL Unvented Gas Logs THERMOSTAT CONTROL LIGHTING INSTRUCTIONS 1. STOP! Read the safety information. 2. Make sure the manual shutoff valve is fully open. 3. This heater is equipped with an ignition device (piezo) which automatically lights the pilot. 4.
  • Page 24: Safety Checklist

    SAFETY CHECKLIST 18/24/30VL Unvented Gas Logs Continued safe operation of this appliance requires, but is not limited to, these "Do's" and "Don'ts": DO'S 1. Do connect the appliance only tot he type of gas for which it is equipped to burn. 2.
  • Page 25: Maintenance

    MAINTENANCE 18/24/30VL Unvented Gas Logs The appliance and fireplace should be inspected before use and at least annually by a professional service Never force a drill, wire or any object into the person. More frequent cleaning may be required due orifice of the pilot spud.
  • Page 26 MAINTENANCE 18/24/30VL Unvented Gas Logs If this appliance is installed in a solid-fuel burning If the appliance is moved even slightly , during fireplace with the flue damper open, a qualified service cleaning or log replacement, check for gas leaks. person should examine and clean the venting system Repair any gas leak before resuming normal of the solid-fuel burning fireplace at least once a year,...
  • Page 27: Troubleshooting

    TROUBLESHOOTING 18/24/30VL Unvented Gas Logs While the manufacturer has made every reasonable effort to insure this appliance operates properly and satisfactorily, sometimes problems do arise. The following troubleshooting chart lists several problems with their probable cause and solution. Any adjustments and/or replacements must be made by a qualified person.
  • Page 28: Replacement Parts

    REPLACEMENT PARTS 18/24/30VL Unvented Gas Logs Fiber Log Set Refractory Log Set 530501 18/24/30VL parts 11/08 53D0501...
  • Page 29 Also note, your model may use either Five Piece Refractory Logs or Five Piece Fiber Logs. These different log types shall not be mixed. Item Description Qty. 18VL 24VL 30VL 1. Pilot Assembly (Nat.) Manual/T-stat 26D2529 26D2529 26D2529 1.
  • Page 30 18/24/30VL Unvented Gas Logs 53D0501...
  • Page 31: Warranty

    Gas Logs Limited Warranty 18/24/30VL Unvented Gas Logs What is covered and for How Long MHSC will make available replacement parts for parts that are defective according tot he following terms. Logs - A free replacement will be made available at our factory for any logs if they fail due to deterioration within two (2) years of the verified purchase.
  • Page 32 MHSC 149 Cleveland Drive • Paris, Kentucky 40361 www.mhsc.com...