Stove Vent Connection - Napoleon GDS3700-N Installation And Operation Instructions Manual

Gas-fired gravity direct vent wall furnace
Table of Contents

Advertisement

10
FIGURE 15
of the chimney. Place the flashing over the air terminal and slide it underneath the
sides and upper edge of the shingles. Ensure that the air terminal is properly cen-
tered within the flashing, giving a 3/4" margin all around. Fasten to the roof. Do NOT
nail through the lower portion of the flashing. Make weather-tight by sealing with
caulking. Where possible, cover the sides and top edges of the flashing with roofing material.
9. Apply a heavy bead of waterproof caulking 2 inches above the flashing. Slide the storm collar around the air terminal
and down to the caulking. Tighten to ensure that a weather-tight seal between the air terminal and the collar is achieved.
Attach the other storm collar centered between the air intake and air exhaust slots onto the air terminal. Tighten securely.

STOVE VENT CONNECTION

STOVE VENT CONNECTION
STOVE VENT CONNECTION
STOVE VENT CONNECTION
STOVE VENT CONNECTION
1. Attach the adjustable pipe to the last section of rigid piping. Secure
with screws and seal.
2. Install the 4" aluminum flexible liner to the stove. Secure with 3
screws and flat washers. Seal the joint and screw holes using the high
temperature sealant provided.
3. Run a bead of high temperature sealant around the inside of the
flue collar. Pull the adjustable pipe a minimum 2" into the flue collar.
ENSURE THA
ENSURE THA
T THE SEALANT IS NOT VISIBLE ON THE EXTERIOR PIPES ONCE INST
T THE SEALANT IS NOT VISIBLE ON THE EXTERIOR PIPES ONCE INST
ENSURE THA
ENSURE THA
ENSURE THAT THE SEALANT IS NOT VISIBLE ON THE EXTERIOR PIPES ONCE INST
T THE SEALANT IS NOT VISIBLE ON THE EXTERIOR PIPES ONCE INSTALLA-
T THE SEALANT IS NOT VISIBLE ON THE EXTERIOR PIPES ONCE INST
TION IS COMPLETED. AN OPTIONAL DECORA
TION IS COMPLETED. AN OPTIONAL DECORATIVE BRASS BAND IS A
TION IS COMPLETED. AN OPTIONAL DECORA
TION IS COMPLETED. AN OPTIONAL DECORA
TION IS COMPLETED. AN OPTIONAL DECORA
USE. (ST
USE. (ST
USE. (ST
USE. (STANDARD WITH A GD175 KIT). IN THE EVENT THA
USE. (ST
ANDARD WITH A GD175 KIT). IN THE EVENT THA
ANDARD WITH A GD175 KIT). IN THE EVENT THA
ANDARD WITH A GD175 KIT). IN THE EVENT THAT THE VENTING MUST BE DIS-
ANDARD WITH A GD175 KIT). IN THE EVENT THA
ASSEMBLED, CARE MUST BE T
ASSEMBLED, CARE MUST BE T
ASSEMBLED, CARE MUST BE T
ASSEMBLED, CARE MUST BE T
ASSEMBLED, CARE MUST BE TAKEN TO RESEAL THE VENTING.
GAS INSTALLATION
FIGURE 18
bility, an optional remote wall switch or millivolt thermostat may be installed in a convenient location. Route single strand
millivolt wire through the electrical hole located at the left rear side of the pedestal. The recommended maximum lead
length depends on the wire size:
WIRE SIZE
14gauge
16gauge
18gauge
Attach the two leads to terminals 1 and 3 located on the gas valve
DO NOT CONNECT EITHER THE W
DO NOT CONNECT EITHER THE W
DO NOT CONNECT EITHER THE W
DO NOT CONNECT EITHER THE W
DO NOT CONNECT EITHER THE WALL SWITCH, THERMOST
WS-415-63 / 11.24.98
5. Apply high temperature sealant to the outer edge of the inner sleeve of the air terminal. Slip
a 4" diameter coupler a minimum of 2" over the sleeve and secure using 3 screws.
6. Apply high temperature sealant to the outer edge of the of the outside sleeve of the air
terminal. Slip a 7" diameter coupler over the sleeve and secure as before. Trim the 7" coupler
even with the 4" coupler end.
If the attic space is tight, we recommend adding sufficient lengths of 7" rigid piping, secured
and sealed as necessary.
7. Thread the air terminal pipe assembly down through
the roof support and attach, ensuring that a minimum 16"
of air terminal will penetrate the roof when fastened. The air
terminal must be located vertically and plumb.
8. Remove nails from the shingles, above and to the sides
TIVE BRASS BAND IS A
TIVE BRASS BAND IS AV V V V V AILABLE FOR THIS
TIVE BRASS BAND IS A
TIVE BRASS BAND IS A
AKEN TO RESEAL THE VENTING.
AKEN TO RESEAL THE VENTING.
AKEN TO RESEAL THE VENTING.
AKEN TO RESEAL THE VENTING.
Bring the gas line to the stove through either a hole in the pedestal back or in the floor
area directly beneath the pedestal base. FIGURE 18. Install rigid black pipe, a flex
connector if local codes permit, or 1/2" type L copper tubing with a 3/8" to 1/2" adapter
and a shut-off valve to the stove. FIGURE 19. Seal and tighten securely. The adapter
will be required between the gas valve and the copper tubing or flex connector.
DO NOT KINK FLEXIBLE CONNECTOR.
Check for gas leaks by brushing on a
soap and water solution.
DO NOT USE OPEN FLAME.
Alternate locations for the on-off switch are shown in FIGURE 20. For ease of accessi-
MAX. LENGTH
100 feet
60 feet
40 feet
ALL SWITCH, THERMOSTA A A A A T OR GAS V
ALL SWITCH, THERMOST
ALL SWITCH, THERMOST
ALL SWITCH, THERMOST
FIGURE 17
ALLA-
ALLA-
ALLA-
ALLA-
AILABLE FOR THIS
AILABLE FOR THIS
AILABLE FOR THIS
AILABLE FOR THIS
T THE VENTING MUST BE DIS-
T THE VENTING MUST BE DIS-
T THE VENTING MUST BE DIS-
T THE VENTING MUST BE DIS-
FIGURE 19
T OR GAS V
T OR GAS V
T OR GAS V
T OR GAS VAL
AL ALVE TO ELECTRICITY (110 VOL
AL AL
VE TO ELECTRICITY (110 VOLTS)
VE TO ELECTRICITY (110 VOL
VE TO ELECTRICITY (110 VOL
VE TO ELECTRICITY (110 VOL
FIGURE 16
FIGURE 20
TS)
TS)
TS)
TS)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Gds3700-p

Table of Contents