Pressure Switch Testing And Replacement - Bradford White TW Series Service Manual

Tw series through-the-wall gas water heaters troubleshooting guide and instructions for service
Table of Contents

Advertisement

Pressure Switch Testing
Step 1.
Position power switch on gas control
to the "OFF" position.
Step 2.
Remove the three screws (Phillips screw driver) from control access cover on blower assembly and
remove cover (see photo 1).
Step 3.
Carefully remove pressure switch from blower housing (see photo 2)
With steps 1,2 & 3 complete,
disconnect wire leads from
pressure switch.
Use a multi-meter set to the
ohms setting. With blower off,
check across pressure
switch terminals.
Are switch contacts open?
(no electrical continuity)
Y
Position gas valve power
switch to the "ON" position
and adjust thermostat
to call for heat,
this will start the blower.
Check with multi-meter, do
pressure switch contacts close
with blower running?
Y
Switch contacts are OK.
See safety circuit trace
(page 29)
20
1
Check tubing and pressure tap
N
Y
Check tubing and
pressure tap on
N
N
switch for blockage.
Is there blockage?
TTW SERVICE PROCEDURE III
Pressure Switch Testing and
120 volt potential exposure. Use caution
making voltage checks to avoid personal injury.
Pressure switch
Slide pressure switch in direction of
wire leads
arrow while tilting slightly away
from blower housing.
N
on switch for blockage.
Is there blockage?
Y
Clear blockage
Y
Is vent system length
Is vent
within vent table
N
system
blocked
listed on pages 7 & 8
Reconfigure vent
compliant with
Replacement
WARNING
2
Replace switch
(see page 19)
See blower testing
Y
specifications
Is blower OK?
N
Correct blower
system to be
vent tables.
Pressure Switch
Y
(page 20)
N
problem.
Page 20