LG MFL65003102 Installation Manual page 19

Air conditioner
Table of Contents

Advertisement

2. Install conduit to the wiring knockouts.
Connect power/communication cable to terminal block through the wiring knockouts.
NOTE :
1. Separately wire power supply cord and connecting cable.
2. Use heat-proof electrical wiring capable of withstanding temperature up to 75°C(167°F).
3. Use outdoor and waterproof connection cable NRTL(UL, ETL, CSA...) listed and rated more than
300V for the connection between indoor and outdoor unit. and this cable should be enclosed in
conduit.
After the confirmation of the above conditions, prepare the wiring as follows:
1) Never fail to have individual power specialized for the air conditioner. As for the method
of wiring, follow by the circuit diagram posted on the inside of control box cover.
2) Provide a circuit breaker switch between power source and the unit.
3) The screws which fasten the wiring in the casing of electrical fittings are liable to come
loose from vibrations to which the unit is subjected during the course of transportation.
Check them and make sure that they are all tightly fastened. (If they are loose, it could
give rise to burn-out of the wires.)
4) Specification of power source
5) Confirm that electrical capacity is sufficient.
6) Be sure that the starting voltage is within 10% plus or minus of nameplate voltage rating.
7) Confirm that the cable thickness is as specified in the power sources specification.
(Particularly note the relation between cable length and thickness.)
8) Never fail to equip GFCI breaker when installing the air handler near wet or moist loca-
tions.
9) The following troubles would be caused by voltage drop-down.
• Vibration of a magnetic switch, damage on the contact point, fuse breaking, disturbance by the
normal function of an overload protection device.
• Proper starting power is not given to the compressor.
HAND OVER
Teach the customer the operation and maintenance procedures, using the operation manual.
(air filter cleaning, temperature control, etc.)
NOTE : Openings where field wiring enters the cabinet must be completely sealed.
Lock nut
Conduit
mounting plate
1/2inch(21.3 mm)
Conduit
power cable
communication cable
Installation Manual 19
Installation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents