The RDM-ZC Zero Cross Module is a 2400 W zero-cross relay built for long
term, reliable switching of electronic fluorescent ballasts, electronic trans-
formers and incandescent lamps. It is designed for use with the RDA series
of enclosures, in an AMX Lighting™ modular digital dimming system. The
RDM-ZC module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL
approved.
Mounting points
Zero cross
relay
FIG. 1 RDM-ZC
RDM-ZC UL and C-UL Ratings
• 120-277 VAC, 50/60 Hz, 2400 W
• 240/277 VAC, 50/60 Hz, 2400 W
Suggested Switched Loads
• Incandescent
• Electronic transformers
• HID ballast
• Electronic and magnetic ballast
Specifications
• Dimensions (HW): 10.00" x 2.75" (25.40 cm x 6.99 cm)
• Non-phase dependant
• Use wires rated at 75°C (167°F)
• Torque terminals to 7 in-lbs. (0.8 N/M)
• Max. wire size: 10 AWG (4 mm²)
• Wire stripping length: 0.28" (7 mm)
• Weight: 1.5 lbs. (0.68 kg)
• BTU/hr: 150
• Control current: 45 mA @ 12 VDC
Caution: Pre-Installation Notes
• All Class 1 wiring must be connected to proper terminals.
• All control wiring must be connected to proper terminals.
• Disconnect power while installing or connecting the unit.
• Keep top and bottom air vents clear at all times.
• Test loads for shorts before connecting.
• Use low voltage wires with a 300 volt rating or greater.
• Use field installed copper conductors.
• All electrical ratings are for continuous duty.
• For indoor use only.
Line in (hot)
High-voltage
Load out
connections
Low-voltage control
wiring: 4-pin connector
to AMX Lighting master
controller
Installation Sheet
• This module may require extra power from the AXlink connection or an
external power supply connected to the control card.
Connecting the RDM-ZC to the AMX Lighting Master
Pin 4 (GND)
Pin 3 (RLY)
Pin 2 (DIM)
Pin 1 (+12 V)
RDM-ZC 4-pin module connector
3 (-)
1 (+)
4-pin plug from RDM series module
NOTE: The 4-pin plugs from the module connector to
the 4-pin connector on the master (black plug cover facing up).
FIG. 2 RDM-ZC connections
Lighting Application Drawing
All neutrals are common
to the Neutral block in the
enclosure. Provide a
separate neutral for
each load.
Neutral
Line in (HOT)
Circuit breaker
panel
FIG. 3 RDM-ZC wiring configuration
RDM-ZC Zero Cross Module
2400 W
Zone 1
Load
Incandescent track
lighting
Fluorescent Ballast
BALLAST
BALLAST
Neutral
Load
Neutral
Load
Neon lights
(cold-cathode, on/off)

Advertisement

loading

Summary of Contents for AMX Zero Cross Module RDM-ZC

  • Page 1 It is designed for use with the RDA series of enclosures, in an AMX Lighting™ modular digital dimming system. The RDM-ZC module's 120, 240, and 277 VAC ratings are CE, UL, and C-UL approved.
  • Page 2 043-019-2213 8/01 ©2001 AMX Corporation. All rights reserved. The AMX logo is a trademark of AMX Corporation. AMX Corporation reserves the right to alter specifications without notice at any time. 3000 research drive, richardson, TX 75082 USA • 469.624.8000 • 800.222.0193 • fax 469.624.7153 • technical support 800.932.6993...

This manual is also suitable for:

Rdm-zc zero cross module, 20aRdm-zc