General Information; Technical Information - Biasi Riva ADVANCE SV Owner's Manual

Wall hung gas boiler for central heating supply
Table of Contents

Advertisement

1. General Information

The Riva Advance SV is a high efficiency condensing, wall mounted gas boiler which provides
central heat. The boiler features a gas valve which modulates the energy input from 32,000
BTU/h to 125,000 BTU/h. The boiler is shipped fully assembled. All units are pressure and
combustion tested at the factory prior to shipping.
Key Features:
• Wall mountable - saving valuable floor
space.
• Several flue options available
• Electronic spark ignition
• Safety flow switch - positioned on the
main circuit, which monitors the flow and
protects the main heat exchanger from
thermal shock should there be a lack of
water in the system.
• Frost protection - contains an integral frost
protection system to prevent frost dam-
age which can occur in areas susceptible
to very cold weather conditions.
2. Technical Information (M210.32 CV)
GENERAL
Height
Width
Depth
Weight
ELECTRICAL
Voltage
Frequency
Current
Power consumption
RIVA ADVANCE USER MANUAL
in
31.6
in
15.7
in
13.8
lb
109.5
V
120
Hz
60
A
1.6
W
180
• Boiler operation recognition system -
should the boiler not be used for longer
than 24 hours, it then performs a con-
trolled system test to ensuring the motor-
ized components within the boiler do not
become inoperable due to lack of use.
• Gas valve modulation - the gas input
modulates based off central heating tem-
perature to within ± 2 ºF
• Diagnostic information system equipped
with three LED diagnostic lights for quick
error assessment.
RESTRICTORS
REFERENCES
Natural
Propane
CENTRAL HEATING
Maximum working temp.
Temp. Regulation range*
Maximum pressure
Minimum pressure
Max head loss (at 4.4 GPM)
*At the minimum useful output
Gas
Air
(ø mm)
(color)
N/A
BLUE
548
BLUE
°F
185
°F
100-185
psi
30.0
psi
4.35
ft
8.25
7