Set Temperature Rise - Carrier WeatherMaker 8000 Installation, Start-Up, And Operating Instructions Manual

141 series sizes 050—135 downflow/horizontal induced-combustion
Table of Contents

Advertisement

Table 7—Model 58ZAV Orifice Size and Manifold Pressure for Correct Input
(Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4% per 1000 Ft Above Sea Level)*
AVG GAS
ALTITUDE
HEAT VALUE
RANGE
AT ALTITUDE
(FT)
(BTU/CU FT)
575
600
9001
625
650
to
675
700
10,000
725
750
775
* For size 135-20 only, input is 22,500 Btuh. Deduct 0.1-in. wc from manifold pressure shown in table. Change orifice size if manifold pressure falls below 3.2-in. wc on
altitudes up to 2000 ft, otherwise change orifice size if manifold pressure falls below 2.0-in. wc.
Table 9—Gas Rate (Cu Ft/Hr)
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
10
360
720
1800
11
327
655
1636
12
300
600
1500
13
277
555
1385
14
257
514
1286
15
240
480
1200
16
225
450
1125
17
212
424
1059
18
200
400
1000
19
189
379
947
20
180
360
900
21
171
343
857
22
164
327
818
23
157
313
783
24
150
300
750
25
144
288
720
26
138
277
692
27
133
267
667
28
129
257
643
29
124
248
621
30
120
240
600
31
116
232
581
32
113
225
563
33
109
218
545
34
106
212
529
35
103
206
514
36
100
200
500
37
97
195
486
38
95
189
474
39
92
185
462
40
90
180
450
41
88
176
439
42
86
172
429
43
84
167
419
44
82
164
409
45
80
160
400
46
78
157
391
47
76
153
383
48
75
150
375
49
73
147
367

2. Set temperature rise.

Furnace must operate within range of temperature rise speci-
fied on the unit rating plate. Determine the air temperature rise
as follows.
a. Place duct thermometers in return and supply ducts as near
furnace as possible. Be sure thermometers do not "see" heat
exchangers so that radiant heat does not affect thermometer
readings. This is particularly important with straight-run
ducts.
0.58
0.60
Orifice
Manifold
Orifice
No.
Pressure
No.
43
3.0
43
43
2.7
43
43
2.5
43
43
2.3
43
43
2.1
43
48
3.8
43
48
3.5
48
49
3.8
48
49
3.6
49
SIZE OF TEST DIAL
SECONDS
FOR 1
1
2
5
REVOLUTION
cu ft
cu ft
cu ft
50
72
144
360
51
71
141
355
52
69
138
346
53
68
136
340
54
67
133
333
55
65
131
327
56
64
129
321
57
63
126
316
58
62
124
310
59
61
122
305
60
60
120
300
62
58
116
290
64
56
112
281
66
54
109
273
68
53
106
265
70
51
103
257
72
50
100
250
74
48
97
243
76
47
95
237
78
46
92
231
80
45
90
225
82
44
88
220
84
43
86
214
86
42
84
209
88
41
82
205
90
40
80
200
92
39
78
196
94
38
76
192
96
38
75
188
98
37
74
184
100
36
72
180
102
35
71
178
104
35
69
173
106
34
68
170
108
33
67
167
110
33
65
164
112
32
64
161
116
31
62
155
120
30
60
150
SPECIFIC GRAVITY OF NATURAL GAS
0.62
Manifold
Orifice
Manifold
Pressure
No.
Pressure
3.1
43
3.2
2.8
43
2.9
2.6
43
2.7
2.4
43
2.5
2.2
43
2.3
2.1
43
2.1
3.6
48
3.7
3.4
48
3.5
3.7
49
3.8
INLET
PRESSURE TAP
Fig. 17—Redundant Automatic Gas Control Valve
BURNER FLAME
MANIFOLD
Fig. 18—Burner Flame
b. When thermometer readings stabilize, subtract return-air
temperature from supply-air temperature to determine tem-
perature rise.
c. Adjust air temperature rise by adjusting blower speed.
Increase blower speed to reduce temperature rise. Decrease
blower speed to increase temperature rise.
17
Continued
0.64
0.66
Orifice
Manifold
Orifice
No.
Pressure
No.
43
3.3
43
43
3.0
43
43
2.8
43
43
2.6
43
43
2.4
43
43
2.2
43
43
2.1
43
48
3.6
48
48
3.4
48
ON AND
OFF SWITCH
GAS
PRESSURE
REGULATOR
ADJUSTMENT
MANIFOLD
PRESSURE TAP
BURNER
Manifold
Pressure
3.4
3.1
2.8
2.6
2.4
2.3
2.1
3.7
3.5
A95618
A89020

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

58zav

Table of Contents