Step 8 - Install Accessories; Step 9 - Electrical Connection To Furnace (Air Systems Directly Connected To Furnace) - TOTALINE P707 Installation And Operation Instructions Manual

Heat recovery ventilator
Table of Contents

Advertisement

OUTDOORS
NOTE: DUCT CONNECTIONS MAY VARY,
DEPENDING ON MODEL.
*Pitot tube should be kept at least 12 in. away from fans elbows and dampers to ensure accurate reading.
Step 8 — Install Accessories —
ries. Field-installed accessories include:
• Remote Intellitek control
• Dehumidistat
• Remote override timer
Refer to the accessory installation instructions for more in-
formation. See Fig. 25 for wiring.
Step 9 — Electrical Connection to Furnace
(Air Systems Directly Connected to Fur-
nace) —
When the HRV is directly connected to the
furnace, the furnace may need to be interlocked with the HRV
3 POSITION MODE
SELECTION
SWITCH
CUSTOM DEFROST
MODE JUMPER
SELECTION
NOTE: A wiring diagram of the complete unit is inside access panel.
NOTE: A WIRING DIAGRAM OF THE COMPLETE UNIT IS INSIDE ACCESS PANEL
PLACE PITOT TUBE A MINIMUM OF 18" FROM BLOWER OR ELBOWS
Fig. 24 — Pitot Tube Balancing
Install all accesso-
ACCESSORY CONTROL CONTACT
(OPEN & CLOSES CONTACT
WHEN HRV IS ON/OFF)
DIAGNOSTIC
Fig. 25 — Electrical Connections
9
PITOT
TUBE
PITOT
TUBE
to provide air circulation for the system. Connect the R and G
terminals on the furnace to the COM and N.O. terminals on the
HRV. See Fig. 26 for a wiring diagram. Never connect a
120-vac circuit to the terminals of the HRV control contacts.
Use only low-voltage furnace blower control contacts.
On some older thermostats, energizing the R and G
terminals at the furnace has the effect of energizing Y at the
thermostat and therefore energizing the cooling system. For
these thermostats, use the alternate control contacts wiring. See
Fig. 27.
DEHUMIDISTAT
2 WIRES
LED
OVERRIDE, STAND-BY, CONTINUOUS,
RECIRCULATION & CYCLE/HOUR
15-MINUTE TIMER
15 min.
(UP TO 5 TIMERS)
2 WIRES
MAGNEHELIC
GAGE
MAGNEHELIC
GAGE
DEH UM.
WA LL CTR L
TIM ER
+
-
EDF5 (5MR)
2 WIRES
OVERRIDE CONTROLS / CONTR LES DE LA DEMANDE
HUMIDITY
%
HUMIDIT
OVERRIDE
TIMER / MIN.
ECHANGE
totaline
MODE CONTROLS / CONTR LES POUR LES MODES
FILTER / FILTRE
MODE SPEED
CYCLE
POWER
MODES
VITESSE DU MODE
PER HR/ PAR HRE