Final Checks; Care And Maintenance - Carrier Infinity 50XT-A Installation Instructions Manual

15 seer single-packaged heat pump system with puron (r-410a) refrigerant
Hide thumbs Also See for Infinity 50XT-A:
Table of Contents

Advertisement

COMPRESSOR INTERNAL RELIEF
The compressor is protected by an internal pressure relief (IPR)
which relieves discharge gas into compressor shell when
differential between suction and discharge pressures exceeds 550 - -
625 psi. The compressor is also protected by an internal overload
attached to motor windings.
TEMPERATURE THERMISTORS
Thermistors are electronic devices which sense temperature. As the
temperature increases, the resistance decreases. Thermistors are
used to sense outdoor ambient (OAT) and coil temperature (OCT).
Refer to Fig. 21 for resistance values versus temperature. See Fig.
22 for OCT location.
If the outdoor ambient or coil thermistor should fail, the HP/AC
control will flash the appropriate fault code (See Table 2).
IMPORTANT: Coil thermistor is factory mounted. Check to
insure thermistor is mounted properly. Outdoor air thermistor
(OAT) is field mounted and connected. Verify that the OAT has
been properly installed.
THERMISTOR CURVE
90
80
70
60
50
40
30
20
10
0
0
20
40
TEMPERATURE (DEG. F)
Fig. 21 - - Resistance Values Versus Temperature
THERMISTOR SENSOR COMPARISON
The control continuously monitors and compares the outdoor air
temperature sensor and outdoor coil temperature sensor to ensure
proper operating conditions. The comparison is:
S In cooling mode, if the outdoor air sensor indicates ≥ 10 _F
(- -12°C) warmer than the coil sensor (or) the outdoor air sensor
indicates ≥ 20_F (- -7°C) cooler than the coil sensor, the sensors are
out of range.
S In heating if the outdoor air sensor indicates ≥ 35_F (2°C)
warmer than the coil sensor (or) the outdoor air sensor indicates
≥ 10_F (- -12°C) cooler than the coil sensor, the sensors are out of
range.
If the sensors are out of range, the control will flash the appropriate
fault code as shown in Table 2.
The thermistor comparison is not performed during low ambient
cooling operation.
FAILED THERMISTOR DEFAULT OPERATION
Factory defaults have been provided in the event of failure of
outdoor air thermistor and/or coil thermistor.
60
80
100
120
A91431
If the OAT sensor should fail, low ambient cooling will not be
allowed and the one- -minute outdoor fan off delay will not occur.
Defrost will be initiated based on coil temperature and time.
If the OCT sensor should fail, low ambient cooling will not be
allowed. Defrost will occur at each time interval during heating
operation, but will terminate after 5 minutes.
If there is a thermistor out of range error, defrost will occur at each
time interval during heating operation, but will terminate after 5
minutes.
Refer to the Troubleshooting Chart (Table 7) for additional
troubleshooting information.
Fig. 22 - - Outdoor Coil Thermistor (OCT) Attachment

FINAL CHECKS

IMPORTANT: Before leaving job, be sure to do the following:
1. Ensure that all wiring is routed away from tubing and sheet
metal edges to prevent rub- -through or wire pinching.
2. Ensure that all wiring and tubing is secure in unit before
adding panels and covers. Securely fasten all panels and
covers.
3. Tighten service valve stem caps to 1/2- -turn past finger
tight.
4. Leave Users Manual with owner. Explain system operation
and periodic maintenance requirements outlined in manual.
5. Fill out Dealer Installation Checklist and place in customer
file.

CARE AND MAINTENANCE

For continuing high performance and to minimize possible
equipment failure, periodic maintenance must be performed on this
equipment.
Frequency of maintenance may vary depending upon geographic
areas, such as coastal applications. See Users Manual for
information.