Page 1
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury. When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are attached to the equipment. GMND-SVX01B-EN March 2012...
ATTENTION: READ THIS MANUAL AND ALL LABELS compounds have the same potential impact to the ATTACHED TO THE UNIT CAREFULLY BEFORE environment. Trane advocates the responsible handling of ATTEMPTING TO INSTALL, OPERATE OR SERVICE THESE all refrigerants-including industry replacements for CFCs UNITS! CHECK UNIT DATA PLATE FOR TYPE OF GAS AND such as HCFCs and HFCs.
Page 3
Improper installation, Trane and the Trane logo are trademarks of Trane in the adjustment, alteration, service or use of this product United States and other countries. All trademarks could cause flammable mixtures.
Page 4
Important: It is the equipment owner’s responsibility to provide any scaffolding or other apparatus required to perform emergency service or annual/periodic maintenance to this equipment. GMND-SVX01B-EN...
This should be accomplished by conform with local building codes, or in absence connecting a grounded conductor between the of local building codes, with CGA-B149.1 service panel and the furnace. To ensure a proper “Installation Codes for Natural Gas Burning GMND-SVX01B-EN...
40-1/4 41-7/8 1/2 or 3/4 (1083) (1022) (1064) (152) (156) 48-1/8 45-3/4 47-3/8 1/2 or 3/4 (1222) (1162) (1203) (152) (174) (a) “D” dia. equals the air inlet opening and the flue discharge opening. Figure 3. Dimensions, standard units GMND-SVX01B-EN...
Page 11
At altitudes of 2,000 to 4,500 feet (610 to 1,372 m), the units must be orificed to 90 percent of the normal altitude rating, and be so marked in accordance with the ETL certification. Figure 4. Temperature rise and pressure drop graph GMND-SVX01B-EN...
6” (152 mm) setting cannot be maintained. Failure to follow these Note: When the clearances required for accessibility are greater than the recommendations could result in equipment or minimum required safety clearances, the accessibility clearances property damage. take precedence. GMND-SVX01B-EN...
(P/N 251-07944 and 251-07946) to the unit heater using the holes to which the louvers were attached. 5. Using the enclosed #8-18 x 1/2 screws and with the top panel oriented such that the side with the larger holes GMND-SVX01B-EN...
Page 15
(P/N 251-07945) and to the right side panel (P/N 251-07947). Note: The top and bottom panels must be attached so that the sides with the larger holes are facing the unit heater; this makes the assembly easier. 10. Install the louvers and cone springs. GMND-SVX01B-EN...
Failure to follow these instructions could result in death or serious injury. Before any connection is made to an existing line supplying other gas appliances, contact the local gas company to make certain that the existing line is of adequate size to handle the combined load. GMND-SVX01B-EN...
If gas pressure is excessive on natural gas applications, install a pressure regulating valve in the line upstream a. Manual “A” valve from the main shutoff valve. b. Manual “B” valve c. Solenoid valve d. Pilot safety e. Pressure regulator GMND-SVX01B-EN...
D 3 6 31 C The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system in excess of 1/2 psig (3.5 kPa). GMND-SVX01B-EN...
Equipment” or CAN/CGA-B149.2, “Installation Codes corrosion resistant screws. Two full turns of 3M™ #425 for Propane Gas Burning Appliances and Equipment” . Aluminum Foil Tape or its equivalent must then be used to seal each joint. General Electric RTV-108, Dow GMND-SVX01B-EN...
Page 20
(1 m) from any building opening, and more than four feet (1.3 m) from, and not directly above, any electric meter, regulator, or relief equipment (refer to Figure 10, p. 21 Figure 12, p. 21). GMND-SVX01B-EN...
In most applications, the terminal should be on level with the flue outlet of the unit, less 1/4 inch per foot pitch for condensate drainage toward the outside of the building (see Figure 13, p. 22). Figure 11. Horizontal intake/vent locations GMND-SVX01B-EN...
Add an additional 5- inch pipe, if necessary, so that the base of the exhaust cap will be 16 to 24 inches from the combustion air inlet (see Figure 14, p. 22, Step 2). GMND-SVX01B-EN...
Page 23
Seal the joint between the 5-inch 6 inches of combustible material. pipe and the inlet air cap with silicone sealant to prevent the entry of water (see Figure 16, p. 23, Step 4). GMND-SVX01B-EN...
NFPA No. 70 National Electrical Code and applicable local codes; in Canada, to the Canadian Electrical Code, Part 1 CSA Standard C22.1. Thermostat Heat Anticipator Adjustments. initial heat anticipator setpoint should equal the thermostat’s current amperage draw when the unit is GMND-SVX01B-EN...
Page 25
105°C. Should any high limit wires have to be replaced, they must be replaced with wiring material having a temperature rating of 200°C minimum. GMND-SVX01B-EN...
Shut-Down 1. Turn the valve selector knob to the OFF position. 2. Turn off the electricity. 3. To relight, follow the instructions in “Initial Lighting, ” p. 26 (preceding section). GMND-SVX01B-EN...
Page 27
8A. Main Gas Valve (Honeywell) 8B. Main Gas Valve (White-Rodgers) 9. Honeywell Ignitor 10. Honeywell Pilot Burner 11. Honeywell Pilot Orifice 12. Honeywell Electrode/Sensor Lead 13. Hi Limit Switch (Located on Rear Header Plate of Heat Exchanger, Air Inlet Side) GMND-SVX01B-EN...
Page 28
If the unit is equipped with a pressure regulator on the combination gas valve, follow Step a through Step d (above). If the unit is not so equipped, the propane gas supply system GMND-SVX01B-EN...
Check and test the operational functions of all safety tapping. Turn the manual valve on to apply pressure to the devices supplied with your unit. combination control. Note the pressure reading on the GMND-SVX01B-EN...
Page 32
3. Flue Sizes: 100/175 units: 4” dia. flue outlet Reducer required—to be supplied by installer. 200/250 units: 5” dia. flue outlet (no adapter required). 300/400 units: 6” dia. flue outlet Increaser required—to be supplied by manufacturer. GMND-SVX01B-EN...
TEST FIRE THE UNIT FOR A FEW CYCLES, MAKING 10) mounts on the Mounting Adapter Plate (Item 4)— SURE THAT THE UNIT IS OPERATING using a marker. SATISFACTORILY. • Remove nut (Item 5) that secures the Motor Support Shipping Bracket (Item 6) to the Mounting Adapter GMND-SVX01B-EN...
Please send the following information to your local Parts center; If further assistance is needed, contact the manufacturer’s customer service department. • Model number • Serial Number • Part description and Number as shown in the Replacement Parts Catalog. GMND-SVX01B-EN...
Clean flue. Refer to “Installation: Piping,” p. Insufficient combustion air. Check for obstruction in combustion air inlet cap and piping; “Installation: Piping,” p. Blocked heat exchanger. Clean heater. Air leak into combustion chamber Determine cause and repair accordingly. or draft hood. GMND-SVX01B-EN...
Page 36
Power venter wheel rubbing Realign power venter wheel. housing. Bearings are dry. Oil bearings on power venter motor. (Refer to label on motor.) M. Pilot will not light or will not stay Main gas valve off. Open all manual gas valves. lit. GMND-SVX01B-EN...
Page 37
Cold air is delivered during heater Incorrect manifold pressure or Refer to “Operation,” p. operation. input. Voltage to unit too high. Check motor voltage with fan running. Should be 115 volts Air throughput too high. Refer to “Operation,” p. GMND-SVX01B-EN...
Page 38
MV/PV. X. Hi-Limit switch tripping. Unit is overfiring. Manifold pressure too high; adjust. Burner orifices may be too large: verify/replace if required. Air flow too low. Increase air flow; check fan size. Check for proper voltage. Defective switch. Replace. GMND-SVX01B-EN...
Page 39
Wiring Diagrams Figure 22. Standard wiring diagram for unit with S8600 ignition system GMND-SVX01B-EN...
Page 40
Wiring Diagrams Figure 23. Standard wiring diagram for unit with G770 ignition system GMND-SVX01B-EN...
Need help?
Do you have a question about the GMND-SVX01B-EN and is the answer not in the manual?
Questions and answers